Wiring
Startup & Operation
Do not start the burner if the combustion chamber
contains oil or oil vapor.
Per UL requirements, the control will not turn on if the
CAD cell senses flame during the self-test. If the CAD cell sees light (flame) at the beginning of a cycle, the control will remain in
self-test mode until the CAD cell no longer senses light (flame). The amber LED will blink momentarily
green LED will be on or flashing.
Power ON
Open all manual oil line valves. Close the line switch. (If Red LED turn on constant
See below to reset.)
Self-test 1
The control performs a "boot-up" test to verify internal operation each time power is applied to the black
wire. The amber LED turns on and the test continues for about 5 seconds. If the test fails, the control turns
the amber LED off and repeats this test sequence until successful.
Stand-by
(Thermostat circuit open and/or limit circuit open) If Self-test 1 is successful, amber LED turns off and
control waits for thermostat circuit to close and a limit input.
Call for
Set thermostat to call for heat. Thermostat circuit must be closed and black wire must receive
heat
power from the limit circuit.
Self-test 2
If a failure occurs in this self-check, the control won't start and the amber LED blinks 1 second on, 4 sec-
onds off, until serviced or the problem clears. These failures include CAD cell seeing light, internal failure,
or line voltage <90V. See service section.
© Copyright 2015 - Carlin Combustion Technology, Inc.
Model 50200 Diagnostic LEDs
– Amber OFF
– Amber ON
– Green OFF
– Green ON
– Red OFF
– Red ON
– Amber FLASHING
– Green FLASHING
– Red FLASHING
every 3 to 4 seconds and
, control is in lockout.