AirStage AOUA48RLAVM Instrukcja szybkiej instalacji - Strona 11

Przeglądaj online lub pobierz pdf Instrukcja szybkiej instalacji dla Pompa ciepła AirStage AOUA48RLAVM. AirStage AOUA48RLAVM 16 stron. J-ii series

MCA- Minimum Circuit Ampacity- For selecting wire gauge between circuit
breaker panel and outdoor unit.
GFEB- Ground Fault Equipment Breaker- When required by applicable Code.
Electrical wiring must conform to all Local, State, National or Provincial Codes.
"TL" or "transmission line" cable is connected between the indoor and
outdoor unit X1 and X2 terminal connections.
Cable ground wire MUST BE CONNECTED at each termination point.
Refer to the Installation Manual for complete installation details.
15
"TL" or "transmission line" wiring is referred to as the communication
cable between indoor and outdoor units.
IMPORTANT! THE ONLY ACCEPTIBLE TRANSMISSION LINE CABLE IS HONEYWELL PART NUMBER
P/N 3254, CATALOG NUMBER K00250LW OR K00500LW. THE CABLE IS EASILY RECOGNIZED BY THE
PINK COLORED SHEATHING.
USE OF ANY ALTERNATE CABLE WILL RESULT IN A FORFEIT OF THE COMMISSIONING AND EXTENDED
WARRANTY.
6b
TL wiring may be installed in either a parallel or series arrangement.
(Series shown for illustration.)
16a
"Automatic" addressing require indoor units to be wired as shown below.
Refer to Section 6, "Wiring Rules" in the Installation Manual to ensure
maximum wire lengths are not exceeded.
Connect outdoor unit terminals Z1 and Z2 ONLY when more than one outdoor
unit is being connected to a communication network. (See QIG Step 16a)
8
16
16b