Athena 4000 Series Instrukcja obsługi - Strona 12

Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Kontroler temperatury Athena 4000 Series. Athena 4000 Series 16 stron. Temperature/process controller

Ordering
Codes
4
Sensor Input Code
0 = Thermocouple
2 = RTD
Example
Model 4000-B-E-05C = a controller with a thermocouple sensor input; and SPDT relay output (non plug-in)
for setpoint I; a full scale process alarm for setpoint II; and a thermocouple J input range of 0 to 500°C.
*Not available on 4200

Troubleshooting

Before you call, please look at this section to see if your question is covered here. If you do call for technical
assistance, be ready to supply the following information:
NOTE: Fuse blowing
is not caused by the
controller. Blown fuses
are caused by shorts
in the heater circuit,
and must be corrected
to prevent damage to
the controller.
Symptom.
light, no digital display.
Probable Cause.
- No line voltage input
- Open PC board to back- plate connector
(defective connector)
- Open power transformer
Symptom.
reads ambient
Probable Cause.
- External backplate jumper missing (all
models except "S" and "F")
- Defective relay
- Open heater or heater circuit wiring
12
0
0
-
-
Setpoint I
Output type (Plug-In) Code
B = SPDT Relay, 7 A/5 A
F = 4-20 mAdc
S = Pulsed 20 Vdc
T = SPST SS Relay, 1 A
L = Limit Control*
Setpoint II Alarms
B = High deviation alarm only*
C = Low deviation alarm only*
D = High and low deviation alarm*
E = Full scale process alarm*
complete model number of controller
symptoms of the problem
unusual events, if any, that preceded the problem
remedies you have already tried
Controller dead. No output
No output, step 1 ok, display
-
-
Control Options Code
STANDARD RANGE CODE
O = Proportional
Thermocouple
(Standard)
Code
A = 3-mode (PID)
01F
05C
02F
01C
RTD (3-wire, 100 ohms)
01F
06C
22F
22C
09F
09C
Athena's ZC/PC solid state contactors, Series 19 and 39 SCR
power controllers, can be added to boost ac load switching
capacity.
Check -
Verify 120/240 Vac, 50/60 Hz input voltage. Check
heater for shorts. Look for open breakers or open external
fuse. Remove input power. Check continuity through power
transformer primary. With ohmmeter, read between pins: 8
and 9 for 225 or 450 ohms +/-10% and 8 and 10 for 680 or
1000 ohms +/-10%
Corrective Action
- Replace heater, if shorted
- Restore power
- Replace either power transformer or backplate connector
Check -
If no readings in either step above, remove controller
from housing and repeat resistance measurements as above,
but directly on PC board lands corresponding to pins 8, 9, and
10. Correct readings indicate open PC board to backplate
connector problem. Incorrect readings indicate power
transformer problems.
Visually inspect relay contacts. Heater continuity and wiring
Corrective Action
- Install jumper
- Replace relay if contacts are worn or dirty
- Replace open heater, correct defective wiring
Set Range
Type
0 to +999°F
"J"
0 to +500°C
"J"
0 to +1999°F
"K"
0 to +999°C
"K"
Special Options
000 = None
0 to +999°F
Consult factory for
0 to +600°C
available special options
you may need for your
-199.9 to +199.9°F
application.
-199.9 to +199.9°C
0 to +199.9°F
0 to +199.9°C