Installation Instructions

Operating Instructions

Control Panel Description

Continuous
Display Of
Process
Variable
Continuous
Display Of
Setpoint Or
Indexed
Parameter
Touch Key Group
Pressing The "I"
Button Advances
The Cursor In The
"Index" Group
variable, the probe should be close to the work area.
Some experimenting with probe location is often
needed to find its optimum position.
In a bath process, the addition of a stirrer will help
to eliminate thermal lags. Since the thermocouple is
basically a point measuring device, putting more than
one thermocouple in parallel will provide an average
temperature reading and produce better results In air
heated processes.
NOTE: if controls
with grounded or hot input terminals (not floating), an
isolated thermocouple must be used. Otherwise, when
both input and output are grounded, severe ground loop
currents will result, causing errors and permanent
controller damage.
Standard thermocouple limits of error are ± 4ºF or
0.75% (half that for special) plus drift caused by
improper protection or over temperature. This is far
greater than controller error, but can not be corrected
at the sensor except by selection and replacement. In
extreme case, total system requirements can be met by
offsetting the control to compensate for these outside
errors.
(lncreases)
Raises
The Selected
Variable
with "F" or "S" outputs drive loads
Lowers
(Decreases) The
Selected Variable
12
LED To indicate
Output "Status"
Function Selected
Indicated By LED
"Cursor"
Advanced By "I"
Button
Enters The
Selected Value T
O
Nonvolatile
Memory