INSTALLATION, OPERATION AND MAINTENANCE MANUAL
CARNES COMPANY
448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040
I. MOUNTING
NOTE: For Fan Distribution Units shipped attached to humidifiers also refer to Carnes Humidifier
Catalog 900-0119.
The fan distribution unit must be mounted securely on a level and plumb surface at least four feet below the
ceiling to prevent steam from condensing on the ceiling surface. Allow 30 feet in front of the HXBG for the steam
to be absorbed into the air. Do not mount the units above any item that would be damaged if a water leak were
to develop. The humidifier or fan distribution unit must never be mounted outside or where it may be exposed to
freezing temperatures.
For remote mounted fan distribution units see Tables 1 and 2 below:
Table 1 - Maximum Operating Weight
Model
Weight (lbs.)
HXBG
Table 2 - Fastener Recommendations.
Type of Wall
Wood Studs or Solid Wall
II. CONNECTING THE STEAM HOSE - Remote Units
Copper or Brass Tube is the only acceptable substitute
1. For guidelines on typical steam hose installation refer to Humidifier Installation, Operation and Maintenance
Instructions.
2. The steam hose should be installed so there is a continuous rise from the humidifier to the bottom connection
of the remote unit. Support the steam hose at intermediate points to prevent dips or pockets. If there are any low
point add a "T" fitting to drain condensate.
3. Any turns should have a minimum of 8" to prevent the hose from kinking.
4. Fasten the steam hose to the connection point on the manifold of the remote unit with one of the hose clamps
provided.
5. Push the steam hose through the opening on the top of the humidifier cabinet and slip over the outlet stub on
top of the cylinder. Fasten with the hose clamp provided.
III. CONNECTING THE CONDENSATE RETURN HOSE
- Remote Mounted Units
1. Fasten the condensate return line to the connection point on the manifold of the remote unit with the hose clamp
provided.
2. Follow the steam hose to the humidifier cabinet and secure the return line to the steam hose.
3. Connect the condensate return line from the fan distributor unit to the condensate return line at the top of the
humidifier cabinet.
4. If it is impossible to maintain a drop to the top of the cabinet, it is permissible to run the condensate return
line directly to the air gap drain fitting or some other common drain. If condensate is run to a common drain, a
trap must be incorporated close to the drain to prevent steam and/or hot water from entering.
COPYRIGHT © 2013 CARNES COMPANY
ALL RIGHTS RESERVED
21
1/4" Lag Screws, 1" minimum length
for Carnes Steam Hose or Condensate Hose
(Continued on reverse side of sheet)
Phone: (608)845-6411
4 Fasteners Required
SUPERSEDES 16812-A
FAN DISTRIBUTION UNITS
Model HXBG
Fax: (608)845-6504
16812-B, Page 1