Anderson ANM76 Instrukcja obsługi - Strona 6

Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Palnik Anderson ANM76. Anderson ANM76 13 stron.

7. Burner Operation Data

Maximum input: 1000 kW/m(when air differential pressure across burner is
2.5mbar)
Minimum input: 100 kW/m
Fuel inlet pressure: 3-85 mbar。
High fire flame length: 800mm. (when air differential pressure across burner is 2.5
mbar, the lower air different pressure, the longer flame)
Upstream temperature limit: -30℃ to 400℃
Downstream temperature limit: 850℃
Remark:
Air differential pressure means the air pressure difference between burner inlet
combustion air pressure and chamber; gas differential pressure means gas pressure
difference between burner inlet gas pressure and chamber.
Anderson Thermal Soluions(Suzhou)Co., Ltd
Anderson Thermal Solutions – ANM76 Burner Operation Manual
Fig 1. ANM76 Series Burner Explosion View
4