7. Burner Operation Data
–
Maximum input: 920 kW/m or 110 kW/module(120mm) ( when air differential
pressure across burner is 2.5mbar)
–
Minimum input: 23 kW/m or 2.75 kW/ module
–
Fuel inlet pressure: 3 - 80 mbar。
–
High fire flame length : 1000 mm. (when air pressure difference is 2.5mbar, the lower
air different pressure, the longer flame)
–
Upstream temperature limit: -30℃ to 400℃
–
Downstream temperature limit: 850℃
Remark:
Air differential pressure means air pressure difference between burner inlet
combustion air pressure and chamber; gas differential pressure means gas pressure
difference between burner inlet gas pressure and chamber.
Anderson Thermal Soluions(Suzhou)Co. Ltd.
Anderson Thermal Solutions – ANM77 Burner Operation Manual
Fig 1. ANM77 Series Burner Explosion View
4