Anderson ANX70 Series Instrukcja obsługi - Strona 9
Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Palnik Anderson ANX70 Series. Anderson ANX70 Series 16 stron.
– Humidity, altitude, temperature and presence of damaging corrosive gases of the
supply air.
10.5 Burner Mounting
If the gas or air inlet orientation needs to be changed, need to disconnect the flexible
hose connected to the burner, remove the four bolts on rear cover, then take out rear
cover and rotate to the right position to connect. Then install the four bolts. Re-
connect the piping.
1. Install the flame sensor
Install the flame sensor (UV or flame rod) to the rear cover pipe screw hole or extent
pipe, make electrical connect to the flame controller.
2. Installing the Spark Plug
Install the spark plug into the opening in the rear cover, make electrical connect to
the flame controller, please to be noted that do not apply any grease to the threads
of the spark plug. You can cause bad grounding of the spark plug if you apply grease
to it. Bad grounding of the spark plug results in a weak spark.
3. Burner Mounting
Fix burner flange with bolts to the wall of chamber, different types of burner
dimensions shown in date sheets, make sure that the wall of the chamber is strong
enough to support the weight of the burner.
If necessary, reinforce the area where you plan to install the burner to support the
weight of the burner.
Refractory furnace walls must allow for thermal expansion as recommended by the
refractory supplier – the wall should apply no stress on the burner block or
refractory layer surrounding the burner block.
If the combustor or burner block is shorter than the furnace wall thickness the block
or combustor should be pulled back into the wall. To prevent refractory overheating,
a 45° chamfer should be applied.
Make sure the ceramic fiber is filled between the burner and the chamber wall if
the gap is more than 20 mm.
10.6 Checklist after installation
To verify the system was properly installed, perform the following checks:
– Be sure there are no leaks in the gas lines.
– Be sure all the components, including the flame monitoring and control system,
pressure switch and wiring are properly installed.
– Be sure all components of the spark ignition system are installed and functioning
properly.
– Be sure the blower rotates in the proper direction. If the rotation is incorrect, have
a qualified electrician rewire the blower to rotate in the proper direction.
– Be sure all valves are installed in the proper location and correctly oriented relative
to the flow direction.
Anderson Thermal Soluions(Suzhou)Co. Ltd.
Anderson Thermal Solutions – ANX70 Burner Operation Manual
7