Anderson PBO92 Instrukcja obsługi - Strona 4
Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Palnik Anderson PBO92. Anderson PBO92 8 stron.
ATTENTION:DANGER OF BEEN BURNT
When burner in operation, combustion is severe, so the burner must be fixed. Hoses or cables in area
of the combustion system must be suitable for high temperature, to prevent high temperature failure
or cause safety accidents. Burners should be periodically inspected and cleaned. Copper wire brush
may be used, if necessary, to clean burner head. The burner system should be checked twice a year
for safety operation.
Burner commissioning shall take care of ignition position, minimum and maximum output position.
Following interlocks will cause emergency stop, including gas low pressure, high pressure or low
combustion air pressure, as well as emergency stop is trigged, the main power is out, UV signal
failure or kiln safety conditions (such as high temperature limit, flue system opening, etc.) will cause
the burner lockout. Users need to know the maintenance interval recommended by the
manufacturer and the interval specified by national laws, whichever is shorter.
4. Fuel Information
The following table shows that the combustion involves common gas properties, and the operators
should strictly abide by the safety regulations. Information is provided by the fuel supplier.
Lower Calorific value
O
Composition
Reference conditions
5.
Brief introduction
The PBO92 Series Oxy-Gas Pilot burner is patented by Anderson Thermal Solutions (Suzhou) Co., Ltd.
for combustion control systems using oxy-gas.
The PBO92 Series Oxy-Gas pilot burner is made of stainless steel with an operating temperature not
above 1300 ° C. This burner is designed without spark plugs, with mounting port for flame detectors
at burner back.
Anderson Thermal Soluions(Suzhou)Co., Ltd
Fuel
-requirement
2
Anderson Thermal Solutions – PBO92 Operation Manual
Natural gas
H
=35,900 [kJ/m
U
2.03 O
m³/ NG m³
2
>98% CH
4
1,013.25 mbar, 0°C
2
]
3