Configuration
Each PIR can be reconfigured via Downlink using AT commands.
a. Change of the operating mode
LoRa
Product
ACW-PIR360-I
ACW-PIR90-I
ACW-PIR180-O
ACW-PIR90-O
ACW-ILB30
ACW-ILB100
* ATO120=XX with XX the transmission period in minutes in hexadecimal.
Example, for a period of 10 minutes: ATO120 = 0A
In alarm mode, a frame can be rewound periodically to return the temperature if a T ° C sensor is integrated into the
product, and to obtain Downlink windows.
ATO120 = 0A is recommended for counting mode (one frame every 10 minutes)
ATO120 = 3C is recommended in alarm mode, in order to have a Downlink window every 60min
Sigfox
Product
ACW-PIR360-I
ACW-PIR90-I
ACW-PIR180-O
Mode
Counting
Alarm
Counting
Alarm
Counting
Alarm
Counting
Alarm
Counting
Alarm
Counting
Alarm
Mode
Counting
Alarm
Counting
Alarm
Counting
ATIM_ACW-PIR_UG_EN_V1.4
Registers to modify
ATO101=11 ATO120=XX*
ATO101=19 ATO120=XX*
ATO101=11 ATO120=XX*
ATO101=19 ATO120=XX*
ATO101=01 ATO120=XX*
ATO101=09 ATO120=XX*
ATO101=01 ATO120=XX*
ATO101=09 ATO120=XX*
ATO101=11 ATO120=XX*
ATO101=19 ATO120=XX*
ATO101=11 ATO120=XX*
ATO101=1D ATO120=XX*
Commands
ATO12=0 ATO16=XX
ATO12=1 ATO16=XX
ATO12=0 ATO16=XX
ATO12=1 ATO16=XX
ATO12=0 ATO16=XX