Dispensing Hoses and Nozzles
9.
The unit may or may not be supplied with dispensing hose and nozzle assemblies.
If customer supplied hose assemblies, pylons, reels, safe breaks and nozzles are used they must
comply with the requirements outlined in AS/NZS 222.
Breakaways
9.1
For all dispensers fitted with breakaways, ensure the breakaway is installed between the nozzle
and the high-mast or pylon (if fitted). Any breakaways that have been subject to a break-away
situation should be inspected and refitted or replaced in accordance with the original
manufacturer's instructions.
Setting up the C4000
10.
Once the pump is connected on site, the final setup check and calibration to complete the
installation must be carried out, using the Parameter Switch and Calibration (K-Factor) Switch.
These switches are found on the C4000 Microprocessor Board which is housed in a metal
enclosure located on the left front of the unit below the display panel
Configuration Codes
10.1
The configuration code has been set at Compac and should not be changed
In the event of it being lost and having to be re-entered the configuration is written on the yellow
label on the C4000 processor board cover
Submersible Delay (Sd)
10.2
This is the time delay from when the Submersible pump starts to when the solenoids in the
dispenser open to allow time for the leak detector to reset.
This is factory set by Compac at 005 (five seconds).
If problems are experienced with the leak detector tripping, firstly check that 'Sd' is still set and
then, if necessary, make it longer as follows.
1. Press and release the K factor switch repeatedly until 'Sd' appears on the Dollar display
'dXXX' will appear in the litres display.
2. Continue to press the K factor switch until the number to be changed flashes. Hold the switch
down and this number will then increment.
3. Release the switch when the required number is displayed. The value of the displayed number
will then be stored in the C4000 memory as the Submersible delay.