PROGRAMMING
Default settings
The COMPACT has been factory set with the following default settings.
Battery Voltage
Low battery voltage
End of charge voltage
Equalisation voltage
Absorption time
Auxiliary Contacts
Active during
RESETTING
When the COMPACT is installed the unit will operate to these default settings. These settings suit most
installations and users generally find that they do not need to reprogram these settings. However, in
some situations these values may need to be altered.
At any time the factory default values can be restored by pressing buttons 20, 21 & 22 simultaneously
for a minimum of 2 seconds. Alternatively, disconnecting/reconnecting the battery will restore factory
settings.
Sinewave Inverter, Battery Charger
11.6V for 12V system, 23.2V for 24V system, 46.4V for 48V system.
14.4V for 12V system, 28.8V for 24V system, 57.6V for 48V system.
15.3V for 12V system, 30.6V for 34V system, 61.2V for 48V system.
2 hours
1. Over temperature
2. Overload
3. Over-voltage or Under-voltage on the batteries
4. If the COMPACT has been turned OFF manually or with a fault.
- 11 -