DRIBO Fla 15/60 GB R N Instrukcje montażu, obsługi i konserwacji - Strona 2
Przeglądaj online lub pobierz pdf Instrukcje montażu, obsługi i konserwacji dla Kable i złącza DRIBO Fla 15/60 GB R N. DRIBO Fla 15/60 GB R N 10 stron. Outdoor load disconnectors
Outdoor devices of Fla 15/60 GB R N and Flc GB R
N series are load disconnectors according to the EN
62271-103 standard. They are manually or motor
operated. Motor drives are designed especially for
remote control.
The GB R N series load disconnectors are universal
devices for mounting into the line (on the top of a
pole) or for mounting under the lines (continuous
disconnector or branching).
Maximum temperature
Minimum temperature
Maximum relative air humidity
Maximum wind pressure
Maximum ice or hoar-frost thickness
Typical altitude
For use in higher altitudes please consult the manufacturer.
During transport and handling, disconnectors
may only be lifted at the base frame, never at the
quenching chambers or at the current path or
insulators.
List of necessary tools and tightening torques
Tool
Ring spanner
Engineer's spanner
Socket spanner (GOLA)
Socket spanner (GOLA)
Torque spanner – see the table of tightening torques
Clamping tongs for stainless fixing band (e.g. Bandimex W 001, Band-It)
Stainless fixing band (e.g. Bandimex B 206, Band-It)
Clamp for stainless fixing band (e.g. Bandimex S 256, Band-It)
Tool part / joint
Clamping terminal yokes
Connecting lug bolts (power leads)
A. Installation of disconnector into the line (on the top of a pole)
The disconnector is installed on a concrete pole using two sleeves R 120 (Fig. 2, pos. 9). The prescribed pole
diameter in the point of fixing the device is 220 – 245 mm.
The upper sleeve is provided with a suspension for the middle conductor.
B. Installation of disconnector under the line (continuous, branching)
The disconnector is installed on a concrete pole using two sleeves R 130 (Fig. 1, pos. 9). The prescribed pole
diameter in the point of fixing the device is 240 – 265 mm.
The disconnector is to be positioned on the support in such a way that the height of the connecting conductor
above the ground at the distance of 2 m to the support was not smaller than 5.5 m with regard to the means of
mechanization which may move around the support point.
General
In the Fla 15/60 load disconnectors, disconnecting
takes place in a low-oil volume quenching chamber.
The Flc GB load disconnectors are equipped with a
special sprig quenching mechanism.
The manufacturer does not assume liability for
damage and operating faults caused by not
observing the installation instructions.
Climatic conditions
Handling and storage
Storage is allowed in both indoor and outdoor
spaces. Store devices on a level surface. Protect
devices against damage during transport and
handling.
Device installation on pole
2
°C
+ 40
°C
- 30
%
100
Pa (m/s)
700 (34)
mm
m a.s.l
up to 1000
Size
24
24
17 (16)
30
-
-
width 19 mm, thickness 0.75 mm
width 19 mm
Torque
30 Nm
75 Nm
20