INSTALLATION
U
P
NIT
LACEMENT
Proper unit placement is essential. To ensure safe and effective operation, the location should:
•
Have enough duct width to mount unit with lamp perpendicular to airflow, with the longest duct length for
increased exposure time.
•
Be on the supply air plenum, LOCATION A (preferred), or on the return air plenum, LOCATION B (alternate).
See Figure 1- Unit Replacement.
•
Be able to support the weight of the AeroLogic
the weight, the duct must be re-enforced, to support the weight, before installing.
•
Have a properly grounded, electrical outlet within reach of the unit's power supply cord.
•
Not be mounted under any source of moisture or condensation, such as humidifiers, cooling coils, etc.
•
Not be mounted near any duct openings, joints, seams, etc. If necessary, seal all openings, joints, seams, etc. using
aluminum tape or equivalent ultraviolet resistant material.
•
Prevent exposure of any plastic, rubber or other non-metallic materials, with inadequate resistance to ultraviolet,
such as; plastic drain pans, wiring insulation, flex ducts, humidifiers, filters etc. If necessary, shield all plastic,
rubber or other non-metallic parts using aluminum tape, conduit, sheet metal or equivalent ultraviolet resistant
material.
•
Be free of any components that would be damaged by or interfere with the installation.
•
Be easily accessible for viewing lamp operation through the sight glass assembly.
•
Be easily accessible and allow enough clearance for routine cleaning or maintenance.
•
Be downstream from air filters. Dust particles will reduce the effectiveness of the unit.
6
®
unit. If the duct construction does seem capable of supporting
Figure 1 - Unit Placement