Daikin 2M56GV1G Instrukcja serwisowa - Strona 17
Przeglądaj online lub pobierz pdf Instrukcja serwisowa dla Chiller Daikin 2M56GV1G. Daikin 2M56GV1G 19 stron. 5.6 kw class outdoor unit, removal procedure
Si11-990
Step
3. Removal of the sound
blankets
1
Untie and remove the
sound blankets.
4. Removal of the
compressor
Remove the flange nut
1
and open the terminal
cover. Release the
compressor lead wire.
Unscrew the 3 nuts.
2
3
Heat up and disconnect
the blazed parts.
Warning
Since it may happen
that refrigerant oil in
the compressor
catches fire, prepare
wet cloth so as to
extinguish fire
immediately.
Warning
Ventilate when
refrigerant leaks
during the work.
(If refrigerant contacts
fire, it causes to arise
toxic gas.)
Caution
From the viewpoint of
global environment
protection, do not
discharge the
refrigerant gas in the
atmosphere. Make
sure to recover the
refrigerant gas with
the recovery system.
Removal Procedure
Procedure
Sound blanket
Removal of Sound Blankets / Compressor
(R18545)
(S)
Yellow
Reassembling precautions
Use non-oxidizing brazing
method. If nitrogen gas is
(R10808)
not available, braze the
parts speedily.
In pulling the pipes, be
careful not to over-tighten
them with pliers. The pipes
may get deformed.
In case of the difficulty with a
gas brazing machine
1. Disconnect the brazed part
where is easy to disconnect
and restore.
2. Cut pipes on the main unit
by a tube cutter in order to
(R10809)
make it easy to disconnect.
Note:
Do not use a metal saw for
cutting pipes by all means
because the sawdust come into
the circuit.
The brazed parts are hot
after being disconnected. To
avoid a burn, make sure that
the compressor is cooled
down before removing.
(R10810)
Points
(R10817)
(C)
Blue
(R)
Red
(R11165)
15