Gateway does not power up (LED does not
illuminate)
• Verify that power supply wires are properly installed on
terminals
— Rebel - Line (brown) conductor to terminal TB1-1 and
the Neutral (blue) conductor to terminal TB1-3
— MicroTech III Maverick II - Line (brown) conductor
to terminal TB1A-1, 2, 3, or 4 and Neutral (blue)
conductor to terminal TB1A-5, 6, 7, 8, or 9
• Verify 120V at appropriate terminals
• Verify that power supply is properly connected to the
Gateway
• Contact Daikin Applied
Cell connection cannot be established
• Check antenna connection to magnetic base
• Check antenna connection to 3G/GPRS connection on
Gateway
• Check signal strength through WebIF
• Verify APN settings
• Verify that neither a LAN or Wi-Fi connection has been
established
• Confirm SIM card installation and recognition by gateway
• Contact Daikin Applied
Wi-Fi connection cannot be established
• Check antenna connection to magnetic base
• Check antenna connection to WLAN connection on
Gateway
• Check signal strength through WebIF
• Verify Wi-Fi IP addressing, ESSID, and login credentials
match customer supplied Wireless LAN requirements
• Connect to Wi-Fi network and try to ping the Gateway's
WLAN IP address
• Verify that neither a LAN or Cell connection has been
established
• Contact Daikin Applied
www.DaikinApplied.com
LAN connection cannot be established
• Confirm proper installation of USB to Ethernet adapter
• Verify LED activity on USB to Ethernet adapter
• Verify LAN addressing through Web IP
• Connect to LAN and try to ping the Gateway's LAN IP
address
• Verify that neither a Wi-Fi or Cell connection has been
established
• Contact Daikin Applied
MicroTech III Data Not Showing Up In User
Interface
• Confirm Ethernet cable is plugged into 'ETH' port on
Gateway
• Confirm Ethernet cable is plugged into 'TIP' port on
MicroTech III controller
• Check for LED activity on Gateway's ETH port
• Verify IP address of Eth0 on the Gateway is 192 .168 .1 .40
• Verify IP address of the MicroTech III controller is
192 .168 .1 .42
— On units with software versions later than
2506017500 this can be done at the keypad
• Contact Daikin Applied