3.4 Power Requirements
The sensor should be connected to a compliant stable power supply. The power supply must be
energy-limited to a maximum of 4.2 A. The power supply requirements for the sensor are shown
in Table 3 and Table 4.
Product
Output Type
5000
PMP (Basic)
PMP (Ratiometric)
PMP (Basic Configurable)
PMP (Configurable 3 & 4 wire)
PTX
PDCR (Passive)
PDCR (Linearized)
5600/5700
PTX
5800/5900
PMP (Basic)
PMP (Basic Configurable)
PTX
PDCR (Passive)
PDCR (Linearized)
Product
Output Type
5000
PMP (Basic)
PMP (Ratiometric)
PMP (Basic Configurable)
PMP (Configurable 3 & 4 wire)
PTX
PDCR (Passive)
PDCR (Linearized)
5600/5700
PTX
5800/5900
PMP (Basic)
PMP (Basic Configurable)
PTX
PDCR (Passive)
PDCR (Linearized)
Copyright 2022 Baker Hughes Company.
8 | UNIK 5*00 Series–English
Table 3: Supply Voltage
Supply Voltage
7 to 32 Vdc (12 to 32 Vdc for 0 to 10 V Output)
5 ± 0.5 Vdc
(Maximum Output + 1 V) (7 V Minimum) to 32 V
7 to 36 Vdc
7 to 32 Vdc
2.5 to 12 Vdc
7 to 12 Vdc
7 to 32 Vdc
7 to 32 Vdc (12 to 32 Vdc for 0 to 10 V Output)
(Maximum Output + 1 V) to 32 Vdc
7 to 32 Vdc
2.5 to 12 Vdc
7 to 12 Vdc
Table 4: Supply Consumption
Current Consumption
<3 mA
<3 mA
<3 mA
<20 mA at 7 Vdc decreasing to <5 mA at 32 Vdc
4 to 20 mA (Limited to 30 mA maximum)
<2 mA at 10 Vdc
<3 mA
4 to 20 mA (Limited to 30 mA maximum)
<3 mA
<3 mA
4 to 20 mA (Limited to 30 mA maximum)
<2 mA at 10 Vdc
<3 mA