General Installation Instructions
These instructions should be read carefully prior to any installation and retained after completion for further
reference and maintenance. Please give these instructions to the building owner/occupier after installation.
Important Safety
1.
Before installation, maintenance or lamp replacement, ensure that the mains supply to the luminaire is switched off and the circuit supply fuses are removed or
the circuit breaker is turned off.
2.
It is recommended that only a qualified electrical contractor carries out the installation of this luminaire and that the luminaire is installed in compliance with the
current edition of the IEE Wiring Regulations.
3.
The person carrying out the installation is to check and verify that the total load on the circuit, including that of this luminaire does not exceed the rating of the
circuit cable, fuse or circuit breaker.
4.
Where a luminaire incorporates discharge control gear (inductive load), the circuit capacity and ratings require careful sizing to avoid nuisance tripping of the
protective device used in the installation.
5.
Where applicable, careful consideration should be taken during installation to ensure that all fixings and/or suspensions are of a suitable size for the luminaire
being installed.
Ratings
1. All luminaires are manufactured & tested in compliance with the requirement contained within BS EN 60598 and are CE marked.
2. All luminaires that are of Class 1 construction and that are marked accordingly, MUST be earthed.
3. All luminaires are designed to operate at 230Volts AC -6%/+10% = 216Volts to 252Volts. Do not operate outside these voltages.
4. All luminaires are only suitable for applications within their rated Ingress Protection limits as stated.
5. Max Ambient Temperature 25
o
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
INSTALLATION
•
All leads from this unit are clearly marked
•
Drill a hole in the desired surface (Cut Out - 72mm). Ensure the mounting location provides adequate distance from water pipes, electrical cables, ceiling
joists or other structural obstacles.
•
Bring through supply cable and connect to the Emergency Pack ensuring correct polarity is observed.
Connect as follows:-
•
Connect the battery pack.
•
Insert the emergency pack through the aperture. The pack will require sufficient space behind ceiling to manoeuvre into position. It must not be mounted
near any heat source or where the ambient temperature normally exceeds 25º C.
•
Offer the luminaire through the aperture, bend back the springs and push gently into the ceiling. Do not install the luminaire onto new plaster or wet paint.
•
Energise the permanent (unswitched) mains supply and check the status indictor illuminates and check the mains health operation of the lamp(s) if they
are maintained.
•
Allow the unit to charge for a least one hour before isolating the permanent mains supply to the unit to briefly check the operation of the lamp(s) in the
emergency mode.
Warning
•
Disconnect the mains supply and unplug the battery leads before working on the unit.
•
Failure to comply with these instructions may result in irreparable damage to the emergency control
gear.
•
This product must not be modified in any way as this will negate any Safety approvals, and may
•
render the product inoperable or unsafe. The product must be installed in accordance with the
•
instructions
•
DO NOT deep discharge the batteries pack in emergency output for over a period of 48hrs as this will cause irreparable damage
to the battery.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Page No. 1
Description – 5W Merlin LED Self Test Emergency
Installation Instructions
®
Luminaire Code(s) –
C
PERMANENT LIVE
NEUTRAL
EARTH
Downlight - Non Maintained
AMELED/ER/3NM/ST, AMELED/OA/3NM/ST
(L)
BROWN OR RED
(N)
BLUE OR BLACK
GREEN / YELLOW
Issue 1.0
(continuous)
www.anselluk.com