DSC Classic PC1565 Skrócona instrukcja obsługi - Strona 11
Przeglądaj online lub pobierz pdf Skrócona instrukcja obsługi dla Panel sterowania DSC Classic PC1565. DSC Classic PC1565 18 stron. Security control panels
Features
Basic Programming
Now let's look at how to change some
of the default settings listed on the
previous page. If you are using the
Classic PC1565 as a "bells only"
system, this could be the only pro-
gramming you need to do.
For example, let's look at changing
the entry delay from default 30 sec-
onds to 45 seconds. Entry delay is in
section 005, "System Times", on
page 29 of the Installation Manual.
All entries in section 005 require 3
digits.
To get into engineering programming
mode you must press [*][8] followed
by your engineering code. At default
this will be [5555]. At this point the
keypad will display "Enter Section"
followed by three dashes. Enter the
three-digit number of the section you
want to program, in this case [005].
You will see the digits 030 displayed
indicating the default time of 30
seconds. Enter [045] for the new entry
delay time. If this is the only change
you want in section 005, you can now
press [#] to exit this section and save
the change. If you want to make
another change, ("Exit Delay", for
example), then use the arrow keys
until 120 is displayed (the default
setting).
Features
24
Basic Programming
Connecting A NOVAGARD 2+T
Connecting A NOVAGARD Delta
Economy
Wiring SAB
Wiring
9