1. Input Current Limiting: The UPS shall be equipped with a system designed to limit the
battery recharge current to conform to UL924 standard.
2. Modular Assembly: The rectifier/battery charger assembly shall be constructed of mod-
ular design to facilitate rapid maintenance.
3. Charging Levels: The battery charging circuitry shall be capable of being set for auto-
matic battery recharge operation, float service and equalizing operation.
4. Temperature Compensated Charging: The battery charger shall be equipped with a
temperature probe to enable temperature compensated charging and adjust the battery
float voltage to compensate for the ambient temperature using a negative temperature
coefficient of 3 mV per cell per degree Celsius at a nominal temperature of 25°C.
5. Capacity: The rectifier/battery charger shall have sufficient capacity to support a fully
loaded inverter and fully recharge the battery to full capacity in accordance with UL 924
specifications.
C. Static Bypass: The static bypass transfer switch shall be solid-state, rated for continuous 100%
duty and shall operate under the following conditions:
1. Uninterrupted Transfer: The static bypass transfer switch shall automatically cause the
bypass source to assume the critical load without interruption after the logic senses one of
the following conditions:
2. Inverter overload exceeds unit's rating
3. Inverter failure
4. Automatic Uninterrupted Forward Transfer: The static bypass transfer switch shall au-
tomatically forward transfer power from the bypass to the rectifier / inverter, without inter-
ruption, after the UPS inverter is turned "ON", after an instantaneous overload-induced re-
verse transfer has occurred and the load current returns the UPS's nominal rating or less.
D. Microprocessor Controlled Logic: The full UPS operation shall be provided through the use of
microprocessor controlled logic. All operation and parameters are firmware controlled. The logic
shall include a self-test and diagnostic circuitry such that a fault can be isolated down to the print-
ed circuit assembly or plug-in power assembly level.
Title: Micro
07
Doc No.: 018-1000-02
Description: Emergency Lighting Inverter User's Manual
Phone :
Fax:
Rev: NR
Website:
Date: 07/26/2016
E-Mail: