Auber Instruments SWA-2451B Instrukcja obsługi - Strona 4

Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Kontroler temperatury Auber Instruments SWA-2451B. Auber Instruments SWA-2451B 6 stron.

Auber Instruments SWA-2451B Instrukcja obsługi
AUBER INSTRUMENTS
Table 2. System parameters.
Mode 2: Press ▲ key for 3 seconds then release
Code
Sign
Description
Sp
SP
Set Value
Mode 5: Press SET key for 3 seconds then release
AL1
Alarm 1 setting
AL1
AL2
Alarm 2 setting
AL2
SC
Input offset
SC
P
Proportional Constant
P
I
Integral time
I
Derivative time / delay
d
D
time
At
Auto-tune
At
t
Cycle time
t
Hy
Hysteresis band
Hy
Alarm 1 hysteresis
Hy1
Hy1
band
Alarm 2 hysteresis
Hy2
Hy2
band
dP
Decimal point position
dP
ALP1
ALP1
Alarm 1 definition
ALP2
ALP2
Alarm 2 definition
CooL COOL

Cooling control

outh
outH
Output high limit
Lock
Lock
Configuration privilege
Sn
Sn
Input type
OPA
Output Mode
OPA
DIL
Input low limit
dIL
DIH
Input high limit
dIH
CF
Display unit
CF
Mode 3: Press ▼ key for 3 seconds and release
TE1
Timer 1
tE1
Te2
TE2
Timer 2
Timer unit and timer
UPT
UPT
mode
INT
Timer control mode
INT

4.3 Control action explanations

4.3.1 PID
The values of the P, I, and D parameters are critical for good response time,
accuracy and stability of the system. Using the Auto-Tune function to
automatically determine these parameters is recommended for the first time
user. If the auto tuning result is not satisfactory, you can manually fine-tune the
PID constants for improved performance.
Proportional Constant (P): P is also called the proportional band. Its unit is
the degree of temperature. For example, P = 50 means the proportional band
is 50 degrees. Assuming the set temperature SV = 200. When integral, I, and
derivative, d, actions are removed - the controller output power will change
from 100% to 0% when temperature increases from 150 to 200 ° C. The
smaller the P value is, the stronger action will be for the same temperature
difference between SV and PV. Please note: for on/off control mode, P is
set to 0.
Integral time (I): Brings the system up to the set value by adding to the output
that is proportional to how far the process value (PV) is from the set value (SV)
2021.01
Initial
Setting Range
Remark
Setting
Decided by DIL, DIH
100
-1999 ~ +9999 ˚C or ˚F
999.9
-1999 ~ +9999 ˚C or ˚F
0.0
-20 ~ 20
0.0
0.1 ~ 200.0
15.0
0 ~ 2000
240
0 ~ 200
30
On/off
Off
2 ~ 120
2 or 120
0.1 ~100.0
1.0
0.1 ~100.0
1.0
0.1 ~100.0
1.0
0 or 1
1
0 ~ 4
0
0 ~ 4
1
On/Off
Off
0 ~ 100%
100
0 ~ 50
0
See Table 3
K
0
0
-1999 ~ DIH
0.0
dIL ~ 9999
999.9
C, F
C
0 ~ 9999
10
0 ~ 9999
0
0 ~ 3
0
0 ~ 8
1
and how long it has been there. When I decreases, the response speed is
faster but the system is less stable. When I increases, the response speed is
slower, but the system is more stable. When I = 0, the integration is turned off.
It becomes to a PD controller that is useful for very slow system.
Derivative time (d): Responds to the rate of PV change, so that the controller
can compensate in advance before |SV-PV| gets too big. A larger number
increases its action. Setting d-value too small or too large would decrease
system stability, causing oscillation or even non-convergence. Normally, d is
4.2.1
set to ¼ of the I value. However, when the controller is in on/off mode (P = 0)
and cooling control is turned on, d means Delay Timer of the Anti-Short Cycle
4.10
Delay (Asd) function. The delay time ranges from 1-200 minutes. (See 4.3.3
for details).
4.3.1
4.3.2 On/off control mode
It is necessary for inductive loads such as motors, compressors, or solenoid
valves that do not like to take pulsed power. It works like a mechanical
4.2.3
thermostat. When the temperature passes the SV+Hy, the heater will turn off.
4.4
When the temperature drops back to SV-Hy, the heater will turn on again. (In
cooling mode, the cooler turns on when temperature passes SV+Hy, and turns
4.2.2
off when temperature drops back to SV-Hy). To use the on/off mode, set P =
0 and Hy to the desired band. Then I and D parameters are not used when
4.2.1
controller is in heating mode. It can be left at any value. In the cooling mode,
the D value is used for Anti-Short Delay time. Its value is in minutes (See 4.3.3
for details).
4.6
4.3.3 Cooling control
4.2.1
When controller is used for cooling control and load is a compressor, it should
not turn on the compressor when its refrigerant is at high pressure (just after
4.10
turned off). Otherwise, the compressor can be damaged in short time. Two
methods are commonly used to prevent the rapid cycling of the compressor.
4.12
One is to use on/off control mode (instead of the PID control mode) with wide
4.13
enough hysteresis band, and long cycle rate. The other is to use the Anti-Short
Cycle Delay (ASd) function. ASd establishes the minimum time that the N.O.
4.5
contacts remain open (after reaching cutout) before closing again. The delay
4.9
overrides any Load Demand and does not allow the N.O. contacts to close until
the set time-delay value has elapsed. ASd gives time to release the refrigerant
4.7
pressure through evaporator. This controller allows the user to use both
methods to protect the compressor. You should set the P = 0 for on/off mode.
4.11
Hy should not be less than 2 degrees unless you really need a tight control. The
cycle rate should be set for 20 second or longer. The D is typically set to 4- 6
(minutes).
4.14
4.3.4 Manual mode
Manual mode allows the user to control the output as a percentage of the total
4.15
heater power. It is like a dial on a stove. The output is independent of the
temperature sensor reading. One application example is controlling the strength
4.16
of boiling during beer brewing. You can use the manual mode to control the
boiling so that it will not boil over to make a mess. The manual mode can be
switched from PID mode but not from on/off mode. This controller offers a
"bumpless" switch from the PID to manual mode. If the controller outputs 75%
of power at PID mode, the controller will stay at 75% when it is switched to the
manual mode, until it is adjusted manually. See Figure 3 for how to switch the
display mode. To activate the manual control, pressing the ◄ key for 3
seconds or until the bottom display shows H at the most left digit. The H
indicating the controller is in manual mode. The number at the right is the
percentage of output. Press the ▼or ▲key to adjust the power. To switch back
to PID mode, pressing the ◄ key for 3 seconds or until the H disappeared.
4.4 Cycle time "t"
It is the time period (in seconds) that the controller uses to calculate its output.
e.g. When t = 2, if the controller decides output should be 10%, the heater will
be on 0.2 second and off 1.8 seconds for every 2 seconds. Smaller t values
result in more precision control. For SSR output, t is recommended for 2 (2
seconds).
4.5 Input sensor type for "Sn"
WWW.AUBERINS.COM
P4/6