BEFORE INSTALLATION: Ensure that the component materials of the Valve are
compatible with the media, with regard to corrosiveness, pressure, and temperature.
Valves must be installed in piping systems that comply to the applicable portions of
A.N.S.I. B31 Standard. Special considerations must be taken with respect to pipe line
expansions and contractions and the media expansions and contractions within the
piping system.
NOTE: THIS IS A DIVERSION VALVE, open port pressure must exceed closed port
pressure.
1. Pipe connections to be threaded into these valves should be accurately threaded,
clean and free of foreign material or metal shavings.
2. TFE pipe tape is recommended for use as the pipe joint sealant, especially in
stainless steel valves.
3. Use two wrenches when making the pipe joint. Apply one wrench on the hex pads
nearest the joint being tightened to prevent breaking the retainer-to-body seal.
1. Piping connections to be soldered into these valves should be cut square and then
cleaned with an appropriate cleaner or flux.
2. These valves are designed to be soft soldered. Apply heat with the flame directed
AWAY from the center of the valve body. Excessive heat can harm the TFE seats
and packing. SOLDERING TEMPERATURE NOT TO EXCEED 500ºF. Adjust
packing after joints are cool.
The valve levers are marked showing proper flow direction in respect to lever position at
extreme end of lever travel.
**** CAUTION ****
THREADED END INSTALLATION
SOLDER END INSTALLATION
OPERATION