Duco DucoBox Silent 0000-4305 Instrukcja instalacji - Strona 8
Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Wentylator Duco DucoBox Silent 0000-4305. Duco DucoBox Silent 0000-4305 16 stron.
ENGLISH
04 Wiring
04.A Connector & buttons
CONNECTORS
1
Power 230 VAC
2
Perilex
3
Humidity Boxsensor
4
CO
Boxsensor
2
5
Duco Network Tool
6
Fan
Illustrations and connections may vary depending on product configuration� Incorrect connection or failure
to follow the instructions may result in damage to the connected devices�
HIGH
LOW
INST
04.B Cabling diagram
The DucoBox Silent communicates with slave components through a wireless (RF)
connection� RF components have a maximum free-field range of 350 metres� This
distance will be much less in a building because of obstacles� Therefor you will
need to allow for features such as walls, concrete and metal� All slave components
(except those which are battery powered) also act as repeaters� Signals from com-
ponents that are unable to make a (strong) connection with the master component
are forwarded automatically via no more than one other component (= hop point)�
Please refer to information sheet RF communication (L8000018) at www�duco�eu
for further information�
≥ 30 cm
DucoBox
8
L2000651 Installation guide for DucoBox Silent (Revision N | 13.07.2020)
A
UP
B
ENTER
C
DOWN
D
HIGH
E
LOW
F
INST
Strain relief
It is mandatory to place the
power supply cable in the
slot provided, as shown in the
drawing, before powering up
the DucoBox�
Silent
RF
230 VAC
BUTTONS
230 VAC
RF
User controller
RF obstacle-free zone
Do not place any obstacles causing RF interference or other devices with an RF
connection within a radius of at least 30 cm around the RF component� We take these
to include items such as washing machines, tumble dryers, ironing boards, etc�
6
PE
230 VAC
Blue
Yellow
Red
L
1
N
1
PE
L
2
2
L
3
HIGH
HIGH
LOW
LOW
INST
INST
A
B
C
DUCO RF
Power supply
Wiring
Frequency
Maximum distance
Maximum number
of components
230 VAC
RF
230 VAC
Switch Sensor
Max. of 25 RF components
White
5
4
3
D
E
F
230 VAC
1,5 mm²
868 Mhz
350 m, free field (less
through obstacles)
Up to 25 wireless
components in a
single system
RF