Hoses for use with acetylene only - Grades R and RM . Hoses for use with
fuel gases (including acetylene) - Grade T.
CGA G-1 5.3.3.13 To minimize the withdrawal of liquid solvent, acetylene
should be withdrawn from the cylinder at a rate not to exceed 1/10 (one-
tenth) of the capacity of the cylinder per hour during intermittent use. For
full withdrawal of the contents of the cylinder on a continous basis, the flow
rate should be no more than 1/15 (one-fifteenth) of the capacity of the cylin-
der per hour.
Check valves prevent the reverse flow of mixed gases. Regulator Check Valves
"B" size 830 4199 Oxygen, 830 4200 Fuel. Torch Check Valves "B" size 831
4146 Oxygen, 831 4138 Fuel.
For Maximum Safety Use Flashback Arrestors
Regulator Mounted
Model -78 Resettable
801 0786 "B" Size (Oxy.)
801 0789 "B" Size (Fuel)
UL Listed --- Meets OSHA Requirements --- Comply with ISO 5175
6
IMPORTANT
NOTE
NOTE
IMPORTANT
Regulator Mounted
Model 65
801 0536 "B" Size (Oxy.)
801 0539 "B" Size (Fuel)
Torch Mounted
Model 460
801 1466 "B" Size (Oxy.)
801 1469 "B" Size (Fuel)