[How to connect]
Connect to the AnyWireASLINK transmission line (DP, DN).
DP and DN have polarity, so be sure to connect correctly.
UL style 2103
Two cores of No.24 AWG (black) φ4.1
■Example of mounting an LP connector to the end of the transmission line
Applicable LP connector: LP2-PWH-10P (2P), LP4-WW-10P (4P)
* The following explanatory gure is an example for the LP2-PWH-10P.
Place the lines in the groove so that the black line
(DN) is positioned nearer the hinge side (pin 1) of
the cover, and fold part A onto the part B side, and
then hitch the hook C to x the cover.
Hole to pass clamp through
Clamp
After crimping, check
that the hooks ③ to ⑥
are securely engaged.
For the LP4-WW-10P, perform crimping with pin 1 for DN, pin 2 for DP, and
pins 3 and 4 empty.
Core line finished
outside diameter
φ1.5
Transmission line
Red: DP (+)
Black: DN (-)
Example for BS-K4117M-M18-1K
B
A
Cover
C
With cover mounted
Check that the hooks ①
and ② are engaged.
Insert the body clamp into the hole
of the cover and crimp them with a
dedicated tool.
③ ④
Dedicated tool: LP-TOOL
⑤ ⑥
[Installation Examples]
If you expect you will change the settings, install the unit so that the setting
port is visible.
<BS-K4117-M12-1K>
- Installation hole
radius
<BS-K4117-M18-1K>
- Installation hole
radius
<BS-K4117-M30-1K>
- Installation hole
① ②
radius
CAUTION
When affixing this product, provide enough slack so that cables and connection
connectors are not stressed.
Do not over-tighten screws. Doing so may cause a failure.
[Installation Location]
- Location where this product is not directly subject to vibration or shock
- Location without condensation
- Location where the atmosphere is free of corrosive gas, ammable gas, and
sulfur
- Location far from high-voltage or high-current cables
- Location far from cables and controllers that generate servo, inverter, or other
high-frequency noise
- Location away from direct sunlight
[Precautions for Use]
- This unit is to be used connected to an AnyWireASLINK transmission line.
It will not operate if it is directly connected to the sequence I/O card or the like.
- Use with an appropriate voltage range.
- Include the transmission line provided with this product in the total line length.
-BSK4117M**1K 5/9-
Setting port
φ12.5
Use the toothed washer when affixing.
Tightening torque: 5.9N・m
Setting port
φ18.5
Use the toothed washer when affixing.
Tightening torque: 15N・m
φ30.5
Setting port
Use the toothed washer when affixing.
Tightening torque: 59N・m