[Various settings]
■Item
Address number setting
■Common procedure for address writer operation
Be sure to connect to the AnyWireASLINK master unit to use.
Setting requires the address writer ARW-04 (Ver.04-1.01 or higher).
For details about the operation method, refer to the address
writer's Products Guide.
1. Connect the terminal to the AnyWireASLINK master unit.
Set with the address writer while supplying transmission signal (DP/DN)
and power supply (24V/0V).
Transmission
signal
ASLINKAMP
White: 0V
* Make sure to use a 24V DC stabilized power supply for the power supply to be connected.
2. Setting is required for all terminals.
Open the protective cover of the terminal to be set, and direct the address
writer toward the setting port as shown in Fig. 1 to perform settings
(Bring the emitter as close as possible to the setting port.)
Close the protective cover of terminals that are not to be set.
Emitter
Setting port
LINK
IN
ALM
Fig. 1
Address number setting
T h e a d d re s s n u m b e r i s u s e d t o s e t w h i c h n u m b e r o f t h e
transmission frame to start with for the terminal to occupy.
Set the address number in a range from "0" to "254."
CAUTION
!
The default address-number setting of the terminal is "255," which
means no setting.
If the address number setting is "255," the terminal cannot perform
input/output operations.
Make sure to use the terminal after setting the address number within
the range of "0 to 254."
Example) Addresses with four ber ampli ers connected
AnyWire address
0
1
2
3
Input
"0" "1" "2" "3"
Setting address
Teaching
Parameter setting
AnyWireASLINK
Red: DP
Master
Black: DN
Green:
24V
24V DC*
Open the protective cover
during settings
Setting port
Teaching
Store the status when a work is present and when a work is absent in the
ASLINKAMP.
Carry out setting with the work actually used.
[SET ON setting]
Perform settings while any object
to be detected exists.
[SET OFF setting]
Perform settings while no object
to be detected exists.
[Automatic setting]
If the display setting for the light receiving level is the AD value
display (parameter 08), then "threshold," "hysteresis," "alarm
value Hi," and "alarm value Lo" are automatically set to the
following percentages based on the difference in the AD
values between when a work is
present and when a work is
absent stored during teaching
operation.
Parameter setting
■Change of threshold
Set the threshold of the light receiving level to judge the presence/absence of
detection.
* Difference in the detection state stored in teaching is 100%.
- Address writer (ARW-04): Parameter 01
AD value
0 - 4095
■Change of hysteresis
Set the amount of change in the light receiving value required to turn the
detection state from ON to OFF.
- Address writer (ARW-04): Parameter 02
AD value
0 - 4095
■Alarm value Hi setting
Set an upper limit for the alarm judgment value.
* Set the alarm values so that Hi is greater than Lo.
- Address writer (ARW-04): Parameter 03
AD value
0 - 4095
* Setting scope depends on the setting of parameter 8.
■Alarm value Lo setting
Set a lower limit for the alarm judgment value.
* Set the alarm values so that Hi is greater than Lo.
255
- Address writer (ARW-04): Parameter 04
AD value
0 - 4095
■Alarm value monitor time setting
Set a monitor time for the alarm judgment value.
- Address writer (ARW-04): Parameter 05
Variable
3 - 255
-L*F1011 7/11-
Work
Threshold
Hysteresis
Alarm value Hi
Alarm value Lo
0 - 100%
Default: 50 (AD value)
0 - 100%
0 - 100%
Default: 5 (AD value)
0 - 100%
0 - 100%
Default: 0 (AD value)
0 - 100%
0 - 100%
0 - 100%
Default: 0 (AD value)
Unit
Default: 50
100ms
AnyWireASLINK
Red: DP
Master
Black: DN
Green:
24V
White: 0V
AnyWireASLINK
Red: DP
Master
Black: DN
Green:
24V
White: 0V
50%
5%
80%
20%