Anywire ASLINKER BL2LN87SB-02DS-CC20 Instrukcja obsługi systemu - Strona 19

Przeglądaj online lub pobierz pdf Instrukcja obsługi systemu dla Adapter Anywire ASLINKER BL2LN87SB-02DS-CC20. Anywire ASLINKER BL2LN87SB-02DS-CC20 20 stron.

[Specifications]
■General speci cations
Operating ambient
0 – +55°C, 10 – 90%RH No condensation
temperature/humidity
-25 – +75°C, 10 – 90%RH No condensation
Storing ambient
temperature/humidity
Based on JIS B 3502 and IEC 61131-2
Vibration resistance
Based on JIS B 3502 and IEC 61131-2
Shock resistance
No corrosive gas
Atmosphere
Operating altitude *
0 – 2000m
1
Pollution level *
2 or less
2
*
1 Do not use or store AnyWireASLINK devices in an environment where the pressure exceeds
the atmospheric pressure at an altitude of 0 meters. Doing so may result in malfunction.
*
2 "Pollution level" is an index that indicates the degree of occurrence of conductive substances
in the environment where the device is used.
Pollution level 2 means the occurrence of only pollution by non-conductive substances.
In such an environment, however, electrical conduction could occur due to accidental
condensation.
■Transmission speci cations
Service power supply voltage
Transmission method
Synchronization method
Transmission procedure
Connection mode
Number of
connection points *
3
Number of connection units
RAS function
*
3 The number differs depending on the master unit. Be sure to refer to the manual of the
master unit for the number.
■Speci cations of the cable included in ASLINKER
LINK
IN0
IN0
IN1
ALM
IN1
[Outside Dimensions]
9.2
4.5
7.1
24V DC +15% to -10% (21.6 to 27.6V DC)
with a ripple of 0.5Vp-p or less
DC power supply superimposed
total frame/cyclic method
Frame/bit synchronization method
AnyWireASLINK protocol
Bus type (Multi-drop method, T-branch
method, Tree branch method)
Number of bit points:
512 points max.
(Input: 256 bits, Output: 256 bits)
Number of word points:
1024 words max.
(Input: 512 words, Output: 512 words)
Up to 128 units
Detection of transmission line disconnection,
transmission line short-circuit, transmission
power supply drop, and
duplicated/unregistered ID
①Transmission side
Number of
Signal name
Core wire size
core wires
DP (Red)
DN (Black)
4
AWG24
24V (Green)
0V (White)
(200)
-BL2LN87SB02D*CC20 19/20-
■Individual speci cations
Number of
occupied points
Response time *
5
Detection
function
Current
consumption
Weight
*
4 It depends on lot No. whether alarm bits can be used or not.
*
5 Indicates an internal processing time required for this unit to recognize a signal change,
apart from transmission delay time (2-cycle time).
*
6 Indicates a value assumed when all IN-0VL pins (NPN) or 24VL-IN pins (PNP) are
short-circuited. To connect a 3-wire type sensor, add a total current consumption of the
sensor.
Core wire sheath
Number of
Signal name
outer diameter
core wires
IN (Black),
24VL (Brown),
φ1.1mm
0VL (Blue)
60
56
Bit input: 2 to 4 points
(Input: 2 points + Alarm bit: 2 points
1ms max.
Slave unit voltage drop (DP-DN voltage drop)
I/O disconnection
I/O short-circuit
I/O power supply drop (24V-0V voltage drop)
Transmission side (DP-DN): 1.6mA
I/O side *
(24V-0V): 11.6mA
6
60g
②Input side
Core wire sheath
Core wire size
outer diameter
3
AWG26
φ1.0mm
(200)
*
4
)
Unit: mm
4.5