[Connection Example]
24V DC stabilized
power supply for
general-purpose
Install an AnyWire
MONITOR
dedicated power
supply to supply to
the entire system.
24V
24V
LG
24V DC stabilized
power supply set
voltage 26.4V.
Select capacity 1.3
times of required
consumption
current.
Transmission line consists of
four wires including power
supply by our at cable
(FK4-075-100).
Under this condition, number
of units of A027XB-02□2-P
connectable to
AB023-□□□ is up to 128
units per one system.
■Transmission distance
within the maximum length
of 100 m
* The total length refers to
the total of the used cables.
When connecting 128 units, refer to
Master
the following con guration as an
example of using power ef ciency
most ef ciently.
10m
or less
40-42 units
30m or less
CAUTION
The terminator (AT0) is a composite element to
stabilize the transmission wave form.
Connect it at a position at the furthest end from
the master in the transmission line.
Note that it has own polarities.
(The LED lights up in a normal state.)
Improper connection may cause a malfunction
or a failure.
Compatible Open Bus
Type
Connector layout
AB023-C1L
CC-Link
Bit distribution I/O
Input: 256 points
Output: 256 points
terminal
AB023-D1
DeviceNet
Input: 256 points
Bit distribution I/O
terminal
Output: 256 points
SET
Open Terminal
RDY
LINK
SET
DP
DP
0V
DN
DN
■ Terminal layout
24V 24V DP DP
LG
0V
DN DN
24V
: Green
0V
: White
DP
: Red
DN
: Black
A027XB-02□2-P
1
2
LINK
4
8
16
32
64
128
ON
ADDRESS
24V
: Green
0V
: White
DP
: Red
DN
: Black
A027XB-02□2-P
1
2
LINK
4
8
16
32
64
128
ON
ADDRESS
24V
: Green
0V
: White
DP
: Red
DN
: Black
In order to turn ON the eject
check switch without fail, tilt
the lever at least approximately
30°or more.
The lever is allowed to be tilted
in any direction.
CAUTION
Terminator AT0
LED
Black (DN)
White (DP)
●Transmission line (Bitty line)
CAUTION
●Installation of transmission lines
Keep route transmission lines away from high-voltage and power cables.
Assign one transmission cable to one system of AB023-□□□. If multiple systems are used, assign a cable to each system.
●AnyWire transmission line error
When the transmission line is not working properly, output is reset.
●Power supply to the AnyWire System
Install an AnyWire system-dedicated power supply to provide 24V DC power.
■Wiring of POKA-YOKE Terminal
○Use the cable with a connector protruding from the back
of the unit.
○Connect the cable, being careful not to reverse the
connection or cause a short circuit.
○When swaging by the link connector, we recommend
A027XB-02G2-P
using a dedicated tool that can realize stable work
ADDRESS No.
quality.
(L-TOOL-N: SUZUDEN CORPORATION)
CAUTION
Eject indicator lamp
Pay attention to crimping direction of the link connector.
Improper connection results in malfunction or failure.
The hinge part side of the connector cover is the black line.
Eject check switch
(Lever type)
For details of link connector pressure welding work, refer to "How to pressure-weld link connector to at cable" in our separate manual.
(Contact our Sales Department.)
A027XB-02G2-P
ADDRESS No.
If a shock of 0.49 G or greater is applied to the
eject check switch, it may cause damage.
Do not force the lever, such as by "twisting it"
or "pulling it downward." Doing so may damage
the eject check switch.
-A027XB02*2P 2/5-
Connect transmission lines DP and DN correctly.
If multiple systems are combined by a multi-wire cable, a malfunction may occur.
When making the connection, make sure that the
cable is not under tension.
In addition, do not x the unit while the cable is
under tension.
At time of
terminal treatment
Trunk line side
Manufacturer: Sumitomo 3M Limited
Applicable connector: Link connector
A027XB-02□2-P
Cable used: 0.75mm
2
/4-wire at cable
Applicable connector: FK4-075-100 (100m)
Cable used: 0.75mm
2
/4-wire at cable
Applicable connector: FK4-075-100 (100m)
CAUTION
At time of
intermediate
treatment
Connector cover
Connector cover
Included
1
A027XB-02G2-P
2
LINK
4
8
ADDRESS No.
16
32
64
128
ON
ADDRESS