Danfoss AK-CH 650 Instrukcja serwisowa - Strona 5
Przeglądaj online lub pobierz pdf Instrukcja serwisowa dla Kontroler Danfoss AK-CH 650. Danfoss AK-CH 650 15 stron. Capacity controller for water chiller
Actual Zone
Load shed input 1
Load shed input 2
Liq. Inj. heat exch
No. of compressors
Comp. application
Step control mode
S4 Min 24h
S4 Max 24h
S4 Average 24h
Extra cooling req.
Settings
Main switch
Cap. control mode
Manual capacity %
Control sensor
Reference mode
Setpoint °C
++Zone delay s
+Zone delay s
+Zone band K
Neutral zone K
-Zone band K
-Zone delay s
AK-CH 650 Version 2.0x
2: Manual
3: Alarm
4: Restart
5: Standby
10: Full loaded All capacity cutin
11: Running Capacity control is running
Actual zone for capacity regulation:
0: P0-error
1: - - Zone
2: - Zone
3: NZ
4: + Zone
5: + + Zone
Actual status on Load shed input 1
Actual status on Load shed input 2
Liquid injection can be coordinated with the compressor operation:
0: no coordination
1: Synchronization with compressor operation
2: Last compressor is stopped only after pump down
Defined number of compressors
Select the compressor application required (see AK-CH 650 manual for further details)
0: Single step only
1: 1xComp. w. unloaders + Single step
2: 2xComp. w. unloaders + Single step
3: Comp. w. unloaders only
4: 1xVariable speed + Single step
5: 1xVariable speed + Comp. w. unloaders
6: 2xVariable speed + Single step
Selected coupling pattern for compressors
Sequential: Compressors are cut in/out in strict accordance
with compressor number
Cyclic: Runtime equalisation between compressors
Best fit: Compressors are cut in/out in order to
make the best possible fit to actual load
0: Sequential
2: Cyclic
3: Best fit
Minimum value for S4 temp. For the last 24 hours
Maximum value for S4 temp. For the last 24 hours
Average value for S4 temp. For the last 24 hours
Brine temperature is higher than desired, and the relay "extra cooling" is active.
Main switch:
0: MAN (The compressor capacity will be controlled manually)
1: OFF (The capacity control will be stopped)
2: AUTO (The capacity is controlled by the PI controller)
Manual setting of compressor capacity
The value is in % of total capacity controlled by the controller
Choise of regulation sensor
0: P0
3: S4
Choice of suction pressure reference
0: SP + Ext. Ref + Night + S3 offset: Used if you require override via 0-10V signal, S3
sensor or night setback.
1: SP + Po optimization: Used if you want to optimize the reference from the
refrigeration appliance (network function) which is most used
Setting of required suction pressure in °C
Time delay between step cut-ins in the regulation band over the "+Zone band"
Set in seconds
Time delay between step cut-ins in the regulation band over the neutral zone
Set in seconds
Regulation band over the neutral zone
Neutral zone for suction pressure
Regulation band under the neutral zone
Time delay between step cut-outs in the regulation band under the neutral zone
Set in seconds
Service Guide RC8BV402 © Danfoss 2016-02
Capacity is controlled manually ("Control mode" = MAN)
Capacity control is in alarm condition (fx. alarm on Po Min
or Pc Max)
Capacity control is waiting for elapse of "Restart time"
Capacity control is ready to start
ON:
Regulation
OFF: Controller stopped
5