After installation and before first operation, perform a
commissioning test of an installation or application making
use of FC 302 Safe Stop with MCB 108.
Moreover, perform the test after each modification of the
installation or application, which the FC 302 Safe Stop is
part of.
A passed commissioning test is a necessary condition for
fulfillment of EN 954-1 Cat. 3
application with FC 302 Safe Stop and MCB 108.
The commissioning test:
1. Remove the dual pole voltage supply to MCB 108
inputs by the safety device while the motor is
driven by the FC 302 (i.e. mains supply is not
interrupted). The test step is passed if the motor
reacts with a coast and the mechanical brake (if
connected) is activated.
Safety PLC Connection
Safety PLC Connection
Safety PLC Connection
Safety PLC Connection
Safety PLC Connection
Wire inserting in MCB 108
Wire inserting in MCB 108
Wire inserting in MCB 108
Wire inserting in MCB 108
Wire inserting in MCB 108
Correct wire inserting
130R0362
ISO13849-1 P Ld
of an
*MI33J202*
®
VLT
AutomationDrive FC 300
2. Send Reset signal (via Bus, Digital I/O or
[Reset] key). The test step is passed if the motor
remains in the Safe Stop state and the
mechanical brake (if connected) remains
activated.
3. Reapply dual pole voltage supply to MCB
108 inputs. The test step is passed if the motor
remains in the coasted state and the
mechanical brake (if connected) remains
activated.
4. Send Reset signal (via Bus, Digital I/O or
[Reset] key). The test step is passed if the motor
gets operational again.
5. The commissioning test is passed if all four test
steps are passed.
Do not combine liveparts and PELV
Do not combine liveparts and PELV
Do not combine liveparts and PELV
Do not combine liveparts and PELV
Do not combine liveparts and PELV
systems.
systems.
systems.
systems.
systems.
Wires between X31/9 and Terminal 37 have
Wires between X31/9 and Terminal 37 have
Wires between X31/9 and Terminal 37 have
Wires between X31/9 and Terminal 37 have
Wires between X31/9 and Terminal 37 have
to be short-circuit protected if not inside
to be short-circuit protected if not inside
to be short-circuit protected if not inside
to be short-circuit protected if not inside
to be short-circuit protected if not inside
the cabinet.
the cabinet.
the cabinet.
the cabinet.
the cabinet.
Rev. 2009-07-08