Danfoss RA 2000 Arkusz danych - Strona 2
Przeglądaj online lub pobierz pdf Arkusz danych dla Termostat Danfoss RA 2000. Danfoss RA 2000 9 stron. One pipe steam thermostatic radiator
Również dla Danfoss RA 2000: Instrukcja instalacji (2 strony), Instrukcje instalacji (4 strony)
Data Sheet
Selection and specification
Should water treatment be
used it is essential that dosing
instructions of the manufacturer
are strictly observed. It is
recommended that formulations
containing mineral oil are
avoided.
Valve bodies for two-pipe systems type RA-FN
Valve bodies for one-pipe pumped or gravity systems, type RA-G
2
Radiator thermostats for one-pipe and two-pipe systems
RA2000 thermostatic sensors (4) supplied in separate boxes
Type
Code no.
RA 2910
013G2910
RA 2920
013G2920
RA 2914
013G2914
RA 2912
013G2912
RA 2922
013G2922
RA 2916
013G2916
RA 5062
013G5062
RA 5065
013G5065
RA 5068
013G5068
(1) Temperatures shown are for units with built-in
sensors which are subject to influence from
radiation and flow temperature. Without these
influences, max. temperature is 2 °C higher at de-
sign load condition.
(2) Remote sensors are supplied with all the
capillary tube coiled within the sensor. When
installing the sensor, only the length required
should be uncoiled.
(1)
These valve bodies are supplied with compression
fittings for copper tube to BS 864. When these
connections are removed, a standard BSP screwed
inlet BS 21 remains.
(2)
Kvs-maximum indicates the water flow (Q) with valve
fully open.
(3)
Remote sensors are recommended.
013G3384
013G3386
013G3388
1) Remote sensors are recommended
2) Kvs-maximum indicates the water flow (Q) with valve fully open
When using RA2000 remote temperature adjusters the kv-values stated in the table above must
be reduced by approximately 40% to take into account the different characteristics of these
sensors.
VD.51.Q1.12 © Danfoss 10/2003
Sensor (Max. sensor temperature 60°C)
Built-in
Built-in, tamper proof
Built-in, low temperature range model
Remote sensor, 0 - 2 m capillary tube (2)
Remote sensor, 0 - 2 m capillary tube, tamper proof (2)
Remote sensor, 0 - 2 m capillary tube (2)
Remote temperature adjuster, 0 - 2 m capillary tube (3)
Remote temperature adjuster, 0 - 5 m capillary tube (3)
Remote temperature adjuster, 0 - 8 m capillary tube (3)
(3) Remote temperature adjusters are supplied with
adapters for RA-valves. Adaptors for older valves
can be ordered separately:
RAVL-adaptor, code no. 013G5192
RAV-adaptor, code no. 013G5193
(4) Important note: Do not use any RA2000
sensors with RA-FR bi-directional valve bodies.
kv-value
(m
3
/h at 1 bar pressure drop)
P-band = K
Working pressure = static + differential pressures. The
maximum differential pressure specified is the maximum
pressure at which the valves give satisfactory control. As with
any device which imposes a pressure drop in the system,
noise may occur under certain flow/pressure conditions. To
ensure quiet operation, maximum pressure drop should not
exceed 40 to 45 kPa. The differential pressure can be
reduced by the use of Danfoss differential pressure controls.
Temp. range
Xp = 2K
5 - 26 °C (1)
5 - 26 °C (1)
5 - 22 °C (1)
5 - 26 °C
5 - 26 °C
5 - 22 °C
8 - 28 °C
8 - 28 °C
8 - 28 °C
DKCD