12.
Lower the front flap and remove the anti-discharge paper strip from
between the batteries and their contacts, and ensure the mains power
to the control circuit is switched on.
13.
Press and release the recessed RESET button to ensure the factory
pre-set programme is active.
15.
Establish with the customer the requirements for the operating
mode, and adjust as follows:
Clock type - 24 hour or 12 hour with AM/PM indication.
The factory pre-set is 24 hour. To convert to 12 hour, press and
hold down the NEXT and DAY buttons until the display changes,
then release. (Repeat to return to a 24 hour clock.)
Temperature display - °C or °F
The factory pre-set is °C. To convert to display all temperatures i n
°F, press and hold down the DAY and COPY buttons until the
display changes. (Repeat to return to a °C display.)
16.
Check the existing space temperature by pressing and holding
down the two buttons: NEXT and COPY, until the display changes from
time to temperature.
17a. If the set temperature is below the space temperature, use the
button to raise the set temperature. The flame symbol will appear in the
display. Check that the heating plant operates correctly.
17b. If the set temperature is above the space temperature, use the
button to lower the set temperature below the space temperature. The
flame symbol will disappear. Check that the heating plant does not
operate.
18.
These models are supplied with a factory pre-set programme which will
be active after a RESET has been performed. The pre- s
programme is shown in the chart with the Setting Instructions.
The chart also has spaces for users own times and temperatures a s
required by them.
19.
The time and programme memory are maintained by the batteries
which should last more than two years. Every 24 months the batteries
should be renewed. Internal circuitry retains the time and programme
memory for one minute, long enough for the batteries to be changed.
e