Danfoss DHP-R 7UA HPC EM Instrukcja instalacji - Strona 7
Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Jednostka sterująca Danfoss DHP-R 7UA HPC EM. Danfoss DHP-R 7UA HPC EM 16 stron.
Connecting
⚠
⚠ ⚠
Note! The maximum load may not exceed 50 VA.
Expansion module
The expansion module is mounted in the electric cabinet on the intended rail. If there is no room, the module can be instal-
led in an external, enclosed cabinet and connected with a longer modular cable.
• Set the switches on the front of the expansion module to the TWC position
⚠
• Connect a modular cable between HP CRM Exp.out and HPC EM Exp.in
Hot water return
Connections of expansion module for TWC operation:
Temperature input, T1: Sensor, water heater
Temperature input, T2: Transmitter, hot water return
Analogue output 0-10 V, AO1: -
Relay, DO1: Signal to electric cartridge, hot water (no-potential closure, maximum 6A)
Exp.in: Connection from HPC RM
Exp.out: Connection to possible additional module.
Electric cartridge
⚠
• Connect to DO1.1 to 24 VAC 2.1.
⚠
• Connect DO1.2 to the contactor coil (the relay coil) and further to 24 VAC 2.2.
Sensor, water heater
⚠
• Connect the sensor cable to T1 and GND.
Sensor, hot water return
⚠
• Connect the sensor cable to T2 and GND.
24 VAC 2.1
From Exp.out
Exp.in
water heater
HPC EM
TWC
Exp.out
Start signal for
electric cartridge
24 VAC 2.2
VMILF102
Danfoss – 7