DANLERS EasyZAPP EZ CEFL Uwagi dotyczące instalacji

Przeglądaj online lub pobierz pdf Uwagi dotyczące instalacji dla Przełącznik DANLERS EasyZAPP EZ CEFL. DANLERS EasyZAPP EZ CEFL 2 stron. Ceiling flush mounted switches

DANLERS EasyZAPP EZ CEFL Uwagi dotyczące instalacji
Variants
DANLERS design and manufacture other EasyZAPP Ceiling Flush Mounted
variants, coded by the following order codes:
EZ CEFL 10VDC
Suitable for 1-10VDC ballasts
EZ CEFL DALI
Suitable for DALI ballasts
Troubleshooting
The load will not switch on:
• The LUX setting as specified by the EasyZAPP App is set too low and is inhibiting
the switch.
• The moving body is not emitting more IR than the background.
(Person wearing insulating clothing in a warm environment)
• Person is too far from the PIR switch, see detection diagram.
• Person is moving unusually slowly (perhaps when testing).
• The control unit battery is not engaged (ON).
Switch RED dip switch next to the telejack connector on the control
unit to the DOWN position.
The load switches on when nobody is present:
• Heater causing infra-red variations in a small cold room.
Resite the EZ CEFL control away from heater.
• Please contact DANLERS for further technical support.
Precautions and Warranty
This product conforms to BS EN 60669-2-1, BS EN 55015 and BS EN 60730.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided (protected with the appropriate MCB) 1kV over voltage.
Please ensure that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue, or visit our website.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
08/09/16
EasyZAPP Ceiling flush mounted switches
EZ CEFL
EasyZAPP ceiling flush mounted multi functional devices can be flush mounted into
suspended and plasterboard ceilings (diagram A). EasyZAPP devices incorporate
a passive infra-red quad sensor to detect movement of a warm body within their
detection zone (diagram B) and a photocell to monitor the ambient light level.
Please Note: ALL adjustments are made via a freely downloadable EasyZAPP
App available from the DANLERS website. EasyZAPP products cannot be
configured by DANLERS ControlZAPP or ScheduleZAPP apps.
Upon detecting movement, if the ambient light is dark enough, the EasyZAPP device
will turn the load ON. The ambient threshold can be set to between approximately
30 lux to 1000 lux and infinite lux (photocell inactive) via the 'Brightness' settings on
the EasyZAPP App. If no more movement is detected within a pre-selected time as
determined by the EasyZAPP App, then the EasyZAPP device will turn the load off.
This 'Timeout' or time lag can be set via the EasyZAPP App adjuster between 10sec
and 23hrs 59min 59sec.
Loading
EZ CEFL is suitable for mains switching or DALI switching only.
EZ CEFL can switch up to:
• 10 amps (3000W) of resistive loads
• 6 amps (1500W) fluorescent lamps, high frequency or switch start,
incandescent or mains halogen lamps (recommended with integral safety fuse)
• 3 amps (750W) of electronic or wire wound transformers.
• 2 amps (500W) of low energy lamps: CFL, LED, 2D etc.
• 1 amp (250W) of fans or most metal halide lamps.
Start-up mode and Default settings
When the EZ CEFL is powered up, it will take 1 minute for the circuitry to stabilise
(detection LED flashing) and ensure the output is off, the EasyZAPP device will then
enter its Default Operating Mode.
Please Note: When in the Default Operating Mode the EZ CEFL is set up as an
occupancy switch with a 20 minute turn OFF timeout (time lag) and photocell
disabled.
INS332 EZ CEFL
Installation notes