Dantherm iA/C T Series Podręcznik informacyjny - Strona 11

Przeglądaj online lub pobierz pdf Podręcznik informacyjny dla Klimatyzator Dantherm iA/C T Series. Dantherm iA/C T Series 18 stron. Panel mounted

Dantherm iA/C T Series Podręcznik informacyjny
iA/C T-Series Installation, Operating & Maintenance Manual

Initiating the "TEST" sequence

5.5.2
1. Press L button for 2 seconds and release (Display will begin "Display Mode")
2. Press L&R button simultaneously for 2 seconds and release (Display will show "test")
3. Press L button for 2 seconds and release (Display will show test step)
4. TEST steps
STEP
0
1
2
3
4
5
6
5.5.3

Resetting the controller to factory defaults

1.
Ensure return temperature is displayed otherwise wait 30 seconds
Press L&R button for 15 seconds and release (Display will show "----")
2.
AC-10 iAC 10K 12K Manual Rev D
DESCRIPTION
Display S/W Revision Level
Int. Fan only
Heater
Int. Fan only
Con Fan
Comp. and cond.
Int. Fan only
INT.
LED
HEATER
FAN
X.XX
ON
OFF
T01
ON
OFF
T02
ON
ON
T03
ON
OFF
T04
ON
OFF
T04
ON
OFF
T05
ON
OFF
COND.
COMP
DURATION
FAN
OFF
OFF
10 SEC
OFF
OFF
30 SEC
OFF
OFF
35 SEC
OFF
OFF
20 SEC
OFF
Cycle
30 SEC
ON
ON
75 SEC
OFF
OFF
30 SEC
Page 11 of 18