01AUG 1005GB
Resume
To reach the parameter selecting mode:
Press the ∇-button and the ∆-button for more than 3 seconds.
To select a parameter within the parameter selecting mode:
∇-button →
Select a lower parameter
∆-button →
Selects a higher parameter
To check the selected parameter
Shortly press the M-button. The parameter value is displayed for 1 second
To change the value of the selected parameter
Press the M-button for more than 1 second
Press the ∇-button
Press the ∆-button
Press the M-button again for more than 1 second and the new parameter value is saved.
To return to the operating mode
Press the ∇-button and the ∆-button for more than 3 seconds to return to the operating mode.
Parameter list; NF-8HD standard values in the ( ).
• ∆p -MIN (700 Pa)
• ∆p -MAX (1300 Pa)
• ∆p -Alarm (2300 Pa)
• Puls time (60 ms) #
• Interval time (10s)
• Down-time-cleaning interval (6 s)
• Number of valves #
• Down-time cleaning DTC, number of cycles (6)#
• Delta-P DTCmax only in DTC mode 2 or 3 (1000 Pa)#
• Delta-P DTCmin only in DTC mode 3 (260 Pa)#
• Operating hours
• Languages
• Display range (Pa)
• DTC-mode (2) #
1. Fan solo
2. Fan + Delta-P DTCmax
3. Delta-P DTCmax + Delta-P DTCmin
• Test mode
0: Test OFF
1: Valve test
2: Start test
3: DP-trimming test
4-7: Relay and display test
• Display contrast (68)
• Service – operating hours
• Service – operating hours – alarm limit (3000 h)
• Service – operating hours – code (0)
• ∆p – mode (ON)
• Parameter protection (ON): Marked with #
select a lower parameter value
select a higher parameter value
Cat.20 / Tab. 05.91 / Page 05.011