DanVex DEH-5K Podręcznik - Strona 16
Przeglądaj online lub pobierz pdf Podręcznik dla Osuszacz powietrza DanVex DEH-5K. DanVex DEH-5K 19 stron. Industrial condensing dehumidifiers
6.11 Parameters Code Description
Code
Parameters
Default
R01
50%
Humidity set(dehumidify)
Air damper automatic
R03
50%
close/open value
Air damper humidity
R04
3%
differential
R05
25°C(77°F)
Indoor temp. set
Humidity set
R06
70%
(humidify)
Humidity differential
R07
3%
(humidify)
Air damper automatic
H01
1
close/open
H02
200
Filter alarm hour
D01
40 minutes
Defrost interval
D02
10 minutes
Defrost stop
D03
17°C(62°F)
Defrost start
F01
AC fan speed set
1
Fan set under achieved
F02
1
humidity
FAN1, DC fan motor
500(5V)
F03
speed 1 voltage
FAN1, DC fan motor
600(6V)
F04
speed 2 voltage
FAN1, DC fan motor
700(7V)
F05
speed 3 voltage
FAN1, DC fan motor
800(8V)
F06
speed 4 voltage
FAN1, DC fan motor
900(9V)
F07
speed 5 voltage
FAN2, DC fan motor
400(4V)
F08
speed 1 voltage
FAN2, DC fan motor
500(5V)
F09
speed 2 voltage
FAN2, DC fan motor
600(6V)
F10
speed 3 voltage
FAN2, DC fan motor
700(7V)
F11
speed 4 voltage
FAN2, DC fan motor
800(8V)
F12
speed 5 voltage
P01
RS485-2 Baud rate
0
P02
RS485-2 Address
1
P03
RS485-2 Protocol
0
RS485-2 Communication
O07
status
O09
Software version
O10
Dew point
O11
Absolute humidity
25
Precision
Range
1%
1%-99%
1%
1%-99%
1%
1%-10%
0.5°C(1°F)
5~35°C(41~95°F)
1%
1%-99%
1%
1%-10%
/
0 - no in use
1
1 - in use
1 minutes
0 - no alarm 100-990。1=10hours
1 minutes
30~60 minutes
1°C(2°F)
1~20°C(34~68°F)
1 - low speed
2 - medium speed(DC motor fan:1,2 -
low;3,4,5 - high)
/
3 - high speed(DC motor fan:1,2 - low;3,4 -
medium;5 - high)
1 - turns off 3 minutes later after achieved
the set humidity
/
2 - keeps working after achieved the set
humidity
10(0.1V)
400~950
10(0.1V)
F03~950
10(0.1V)
F04~950
10(0.1V)
F05~950
10(0.1V)
F06~950
10(0.1V)
400~950
10(0.1V)
F08~950
10(0.1V)
F09~950
10(0.1V)
F10~950
10(0.1V)
F11~950
0-4800
1-9600
1~255
0-General open protocol
0 - abnormal / 1 - normal
6.12 RS485-2 Modbus communication protocol
Function code description:
function 03 – read
function 06 – write single
Address
Object
Function Code
0x1001
03/03/16
ON/OFF
0x1002
03/03/16
fan speed
0x1003
03/03/16
air damper close/open
0x1004
03/03/16
humidity set
air damper automatic
0x1006
03/03/16
humidity set
air damper automatic
0x1008
03/03/16
close/open
03/03/16
0x101B
temperature set
03/03/16
0x101C
working modes
0x101D
03/03/16
humidification set
indoor temperature
0x2001
03
sensor
indoor humdity sensor
0x2002
03
external temperature
0x2003
03
sensor
external humidity
0x2004
03
sensor
0x2005
03
fan running time
0x2006
03
failure
0x2007
03
dew point
0x2008
03
absolute humidity
function 16 – write multiple
Read Only or
Byte
Data
Read/Write
0 - OFF 1 - ON
2 bytes
Read/Write
1 - 1st fan speed
2 - 2nd fan speed
2 bytes
Read/Write
3 - 3rd fan speed
4 - 4th fan speed
5 - 5th fan speed
2 bytes
Read/Write
0 - close 1 - open
2 bytes
Read/Write
1~99%
2 bytes
Read/Write
1~99%
2 bytes
Read/Write
0 - not in use 1 - in use
2 bytes
Read/Write
5~35°C
0 - dehumidification
1 - cooling+dehumidification
2 - heating+dehumidification
2 bytes
Read/Write
3 - cooling+humidification
4 - heating+humidification
5 - humidification
2 bytes
Read/Write
1~99%
Read Only
2 bytes
2 bytes
Read Only
2 bytes
Read Only
2 bytes
Read Only
2 bytes
Read Only
1=10 hours
bit0:built sensor failure
bit1:external sensor failure
bit2:filter alarm
Read Only
2 bytes
bit3:minimum absolute
humidity protection
bit4:in defrost
2 bytes
Read Only
2 bytes
Read Only
26