CONTROL BOARD CONNECTIONS #833/834
8 Pin White Connector (two on 834)
7
5
3
1
7 Pin Black Connectors
1 ORANGE - Open Limit Input (Normally open circuit unless gate is opened)
8
2 WHITE - Close Limit Input (Normally open circuit unless gate is closed)
3 BLACK - Motor - Positive during open cycle, Negative during close cycle
4 RED - Motor - Negative during open cycle, Positive during close cycle
6
5 GREEN - Ground (Limit Switch Common)
6 NOT USED
4
7 BLACK - Ground - Battery Negative
8 RED - Battery Positive (+12 VDC)
2
1 Edge 1 Input
2 Edge 2 Input
3 Ground
4 Ground
5 Stop Input (N/C)
}
6 Close Input (N/O)
7 Open Input (N/O)
8 Ground
9 Ground
10 Free Exit Input (recommended telephone entry)
11 Ground
12 Under Gate Loop Input
13 Ground
14 Safety Loop Input
3 Pin Black Connectors (3)
GND Ground
INP
Input (Activates gate when momentarily connected to ground)
12V +12 Volt Output (For powering options - 2 Amps Max.)
Used when the control board is not functioning. Unplug the
motor harness from the main connector and momentarily
insert into the Emergency Bypass Connector to open the
gate. In the event the motor is not disconnected quickly
enough, the blue 15 amp fuse will protect the circuit board
from damage and should be replaced when the original
problem is fixed.
12
3 Button Control Only
Emergency Bypass Connector