4EVAC Compact 500 Instrukcja obsługi - Strona 9
Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Sprzęt bezpieczeństwa 4EVAC Compact 500. 4EVAC Compact 500 15 stron. Voice evacuation system
Hacousto Holland bv
Industrieweg 87
2651BC Berkel & Rodenrijs
4EVAC Compact 500 operation manual
Manual controls
4.2.1. SILENCE
Press to mute the sound of the buzzer in the entire system.
4.2.2. LAMP TEST
Press to verify visual (LEDs) and audible indications (buzzer) of the front panel of local C500.
4.2.3. ZONE selection
Press to select a zone. Press again to deselect.
NOTE: Zone selection will clear automatically after timeout defined in the configuration settings.
4.2.4. RESET
Press to clear your current zone selection.
4.2.5. FUNCTION button
Press and hold the FUNCTION button to enable Access level 2. In access level 2 you are able to manually
change the status of the system by triggering voice alarm message or resetting the system.
NOTE: Press FUNCTION button first and hold it down while pressing another button.
4.2.5.1.
Use this combination in order to trigger the EVAC or ALERT message on the previously selected zones.
If no zones are selected, this will trigger EVAC or ALERT to all zones accessible from local front panel.
Page 9 of 15
FUNCTION + EVAC / FUNCTION + ALERT
Author:
Triggering manual EVAC
DD