Datakom DKG-190 Podręcznik użytkownika - Strona 8

Przeglądaj online lub pobierz pdf Podręcznik użytkownika dla Kontroler Datakom DKG-190. Datakom DKG-190 8 stron. Battery charge controller

Datakom DKG-190 Podręcznik użytkownika
DKG-190 User Manual
SCREEN
Tel: +90-216-466 84 60 Fax: +90-216-364 65 65 e-mail: [email protected] http: www.datakom.com.tr
DESCRIPTION
GENSET VOLTAGE LOW LIMIT ()
Below this limit, the genset phase voltage
is supposed to fail.
GENSET VOLTAGE HIGH LIMIT ()
Above this limit, the genset voltage is
supposed to fail.
TEST TIMER ()
This is the period of test run. The format is
Minute:Second
AC OUTPUT VOLTAGE ()
The AC voltage produced by the controller
is defined by this parameter. The usual
value is 230V
AC OUTPUT FREQUENCY ()
The frequency of the AC voltage produced
by the controller is defined by this
parameter. The usual value is 50 or 60 Hz
DATAKOM Elektronik Ltd.
-8-
V-1.1
(24.03.2015)
MIN
MAX
70V
270V
100V
300V
1
30min
40V
270V
50Hz
60Hz