Mains fail timer
P9
Mains contactor will be off after the delay adjusted with program parameter P9. Mains
fail timer starts counting when mains is off.
Phase order check
P10
0: Mains phase order check disabled
1: Mains phase order check enabled
Test mode timer
P11
Test mode will be deactive at the end of timer adjusted with program parameter P10.
Remote start relay will be de-energises and generator is expected to start.
6. DECLARATION OF CONFORMITY
The unit conforms to the EU directives
-2006/95/EC (low voltage)
-2004/108/EC (electro-magnetic compatibility)
Norms of reference:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)
The CE mark indicates that this product complies with the European requirements for safety,
health environmental and customer protection.
7. TECHNICAL SPECIFICATIONS
Alternator voltage: 170-300 V-AC (Phase-Neutral)
Mains voltage: 170-300 V-AC configurable (Phase-Neutral)
Mains frequency: 30 – 70 Hz configurable
Generator contactor timer: 1 - 40 sec. configurable
Mains contactor timer: 0 - 999 sec configurable
Mains waiting timer: 0 - 999 sec configurable
Mains fail timer: 0 - 999 sec configurable
Cooldown timer: 0 - 999 sec configurable
Remote start delay: 0 - 999 sec configurable
Mains contactor output: 10A @ 250V-AC
Generator contactor output: 10A @ 250V-AC
Remote start output: 10A @ 250V-AC/28V-DC
Operating temperature: -30C to 70 C
Storage temperature:
Maximum humidity: 95% non-condensing.
Dimensions: 70x115x66mm (WxHxD)
Weight: 180g (approx.)
Installation: DIN Rail mounted.
Case material: High temperature, non-flammable ABS/PC
IP protection: IP20
-30C to 80 C
V-1
(24.07.2017)