2.4. Connection

The Actuators KNX S1R-UP are installed in a flush-mounted socket. The connection
is made using a KNX connector on the KNX data bus. In addition, a power supply for
the connected drive or consumer is necessary (output free of potential).
Follow the guidelines and standards for SELV electric circuits
while installing and cable laying of the KNX connection and
inputs!
ATTENTION!
Relays may be switched on when starting the device for the first
time!
The bistable relays used in this product may switch on in case of shock,
e. g. during transportation.
First apply the bus voltage, as this will switch off the relays. Then
switch on the voltage supply of the drive.
The physical address is assigned by the KNX software. There is a button with a control
LED for this on the actuator.

2.4.1. Connection examples

230V drive at the output:
Mains
(230V)
Each terminal contact may be loaded with a maximum of 10 A.
Actuators KNX S1R-UP • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
7
Two 230V consumers at the output:
Mains
(230V)
Technical changes and errors excepted.
Installation and start-up