elsner elektronik 70361 Specyfikacje techniczne i instrukcje instalacji - Strona 3
Przeglądaj online lub pobierz pdf Specyfikacje techniczne i instrukcje instalacji dla Akcesoria elsner elektronik 70361. elsner elektronik 70361 9 stron. Temperature sensor
1.1. Deliverables
•
Housing with display and sensor board
•
Baseplate
Additionally required (not included in the deliverables):
•
Junction box Ø 60 mm, 42 mm depth
•
Frame (for insert 55 x 55 mm), compatible with the switch scheme used in the
building
1.2. Technical specifications
Housing
Colours
Assembly
Protection category
Dimensions
Total weight
Ambient temperature
Ambient humidity
Operating voltage
Bus current
Data output
BCU type
PEI type
Group addresses
Assignments
Communication objects
Measurement range
Resolution
Accuracy*
* Please note the information on Measuring accuracy
The product is compliant with the provisions of EU guidelines.
Plastic (partially painted)
• White, glossy (similar to RAL 9016 Traffic White)
• Matt aluminium
• Charcoal, matt
• Stainless steel
• Special colours on request
Flush mounting
(Wall mounting in junction box Ø 60 mm, 42 mm
depth)
IP 20
Housing approx. 55 x 55 (W x H, mm),
Mounting depth approx. 15 mm
Baseplate approx. 71 x 71 (W x H, mm),
approx. 50 g
Operation -10...+50°C, storage -20...+60°C
max. 95% RH, avoid condensation
KNX bus voltage
max. 6 mA,
max. 10 mA when programming LED active
KNX +/- bus plug-in terminals
Integrated microcontroller
0
max. 254
max. 254
176
-40...+80°C
0.1°C
±0.5°C at -40...+25°C
±1.5°C at -40...+45°C
Temperature sensor KNX T-B-UP • Software version 3.1 and higher