Cookson FDO-A10E Instrukcja obsługi - Strona 4

Przeglądaj online lub pobierz pdf Instrukcja obsługi dla System otwierania drzwi Cookson FDO-A10E. Cookson FDO-A10E 19 stron. Industrial duty fire door operator

The unit is not functional and the brake is released.
(This unit when equipped with the Expansion Module is available with an optional Battery
Back-Up power unit)
This power unit will keep the processor in the controller energized and continue to monitor
the alarm contacts for a change of status for up to 12 hours. With the battery back-up
power unit the door will stay in the open position until the batteries have become depleted,
12 hours have elapsed with no power, or a change of status in the alarm contact has
occured. If one of these events occur, the unit is not functional and the brake will be
released. The door will close without delay. 5 minutes prior to this closure the unit will
activate the output for the sounder strobes to give a pre-closure warning.

IMPORTANT INSTALLATION INSTRUCTIONS

WARNING - TO REDUCE THE RISK OF SEVERE INJURY OR DEATH:
1) READ AND FOLLOW ALL INSTALLATION INSTRUCTIONS.
2) Install only on a properly operating door. A door that is operating improperly could cause
severe injury. Have qualified service personnel make repairs to cables, spring assemblies,
and other hardware before installing this operator.
3) The Firedoor Controller will not close a balance door in the absence of AC power. The door
system must be able to generate a minimum backdriving torqueof 50 in-lbs. at the operator
output shaft. Sticking or binding doors must be repaired. Doors, door springs, brackets and
their hardware may be under extreme tension and cause serious personal injury. Call a
professional door serviceman to move or adjust door springs or hardware.
4) Remove all pull ropes and remove, or make inoperative, all locks (Unless mechanically
and/or electrically interlocked to the power unit) that are connected to the door before
installing the operator.
5) Install the door operator at least 8 feet or more above the floor if the operator has exposed
moving parts.
6) Do not connect the door operator to the source of power until instructed to do so.
7) Locate the control station: (a) within sight of the door, (b) at a minimum height of 5 feet
so small children cannot reach it, and (c) away from all moving parts of the door.
8) Install the Entrapement Warning Placard next to the control station in a prominent
location.
WARNING - TO REDUCE THE RISK OF SEVERE INJURY OR DEATH:
1) READ AND FOLLOW ALL INSTRUCTIONS.
2) Never let children operate or play with door controls. Keep the remote control (where
provided) away from children.
3) Personnel should keep away from a door in motion and keep the moving door in sight
until it is completely closed or opened. NO ONE SHOULD CROSS THE PATH OF A MOVING
DOOR.
9001(7) ECN 1057 4/10/010
THEORY OF OPERATION (CONT.)

IMPORTANT SAFETY INSTRUCTIONS

4