Cool Expert MIC QKL mini 2 Instrukcja instalacji i obsługi - Strona 8
Przeglądaj online lub pobierz pdf Instrukcja instalacji i obsługi dla Kontroler temperatury Cool Expert MIC QKL mini 2. Cool Expert MIC QKL mini 2 13 stron. Cooling system intelligence

-°cool expert
:2. 1 -
MIC QKL mini 2
Correction factors for sensor TL1 and TBL
Room temperature TL1 (Offset tL1)
oL1
W E
Block temperature TBL (Offset tBL)
oBL
W E
Correction factor (oL1), (obL)
The sensor values measured by the controller can be corrected in the range -10 to 10 K / -18 to 17.5
°R. The set correction value is added to or subtracted from the measured sensor values.
Note:
IIn some practical applications, in exceptional cases, when the sensor lines TL1 and TBL are
extendedand cable conductors are missing, the three-wire measurement technique can be replaced
by a two-wire measurement technique. The resistance resulting from this, which is normally
compensated by the three-wire measurement technique, can be compensated by this parameter. If
the two-wire measurement is absolutely essential, the sensors TL1 and TBL are connected to
terminals 7 and 8 as well as 8 and 9. A bridge must be inserted between terminals 6 and 7 as well as 9
Display/hide temperature display
dt
W E
Temperature display "tL1" switched on
Display of the room temperature in operating level 1 under "tL1"
Temperature display "tL1" hidden
Display of the room temperature is hidden after 5 minutes (Display in the display "___") The room
temperature is displayed again by pressing a control button.
-°cool expert
:2. 2 -
MIC QKL mini 2
Attention: Requirement for the usage of the network functions is that each controller is equipped
with a network module. Controller release R19 and later have to be equipped with a network module
release IF3.
Network identification
nId
W E
Adjustable value 1 – 16
The controllers in a network can be linked and separated in up to 16 communication groups.
Controllers with the same identification number can communicate with each other. Precondition is
that they are configured as described below. Up to 128 controllers can be linked in one network.
Network based Communication "Off" (OFF)
Network based communication disabled for this controller.
Temperature communication group
ntG
W E
Value 1 - 8
With ''ntG'' it is possible to balance different room temperature zones in one and the same cooling
position, using a setpoint adaption. Furthermore it is easily possible to assign the capacities of the
evaporators to the capacities of the compressors according to the desired temperature difference
DT1 (room-temperature based central refrigeration plant capacity control). Up to 16 Controllers can
be linked in one temperature-communication-group. Precondition: The controllers belonging to the
same temperature communication group have to be set to the same value of ''ntG'' and ''nId''. For
this purpose all evaporators have to be equipped with a controller. The coordination of the
temperature balancing is done by temporarily adjusting the setpoint temperature. The adapted
setpoint temperature is displayed in the operating level 1 under ''tSA''. The communicating
controllers perceive the new setpoint temperatures and first start their cooler fans followed by their
cooling request, in the event of a tendentiously increasing room temperature. If the remaining
controllers of the cooling position detect a tendentially falling room temperature, their cooling
contactor remains inactive whereas the cooler fans remain switched on. After the controller which
initially requested cooling reaches his setpoint temperature, the cooling request and the cooler fans
are switched off under consideration of minimum runtimes. The air cooler fan management as
configured under ''cFA'' is used again. The original setpoint temperature has now priority even for the
adapted controller.A deviation of the setpoint temperature within a group is limited to max. 8 K / 14.5
°R.In the case of setpoint temperatures above freezing point, the controller ensures that the room
temperature does not fall below 0.5 °C / 32.9 °F.
You can obtain more information on temperature communication with its various possible
applications directly from Cool Expert on request.
Communication of temperature "Off" (OFF)
No network based temperature communication.
Note:
The temperature communication using the digital inputs is disabled when a temperature
communication group is set.
Factory setting
W E
(All temperature values of the factory setting are indicated in Celsius)
0. 0
Correction factor: -10 to 10 K / -18 bis 17,5 °R
0. 0
Correction factor: -10 to 10 K / -18 bis 17,5 °R
(Display temperature)
On
Temperature display "tL1" switched on
OFF
Temperature display "tL1" hidden
(Network identifikation)
1
Adjustable value 1 – 16
OFF
Network based communication "off"
(Network temperature group)
3
Adjustable value 1 - 8
OFF
Temperature communication "off"
The expanded configuration level
Internal heat control
iHC
W E
Heating control activated, value 1-15
Depending on this value the connected defrost heater will be checked in defined intervals. A
value of 1 represents 6 month. Higher values will decrease the interval.
Attention:
Values larger than 5 can possibly affect the control functions in a negative way and should only
be used on behalf of the Cool Expert Service.
No internal heat control (OFF)
Interval checks of the defrost heater are disabled.
Internal standby delay
iSd
W E
Value 1 - 900 seconds
Once a standby signal is cancelled (by digital input or network module), the controller remains
blocked for the programmed duration.
Default standby delay (STD)
The standby delay is set to 8 minutes (480 seconds).
Back to the configuration level (operating level 2)
-2-
Defrost communication group
ndG
W E
Value 1 – 8
Up to 16 controllers can be linked together as a defrost communication group.
Precondition: The controllers belonging to the same defrost communication group have to be set to
the same value of ''ndG'' and ''nId'' . Controllers of the same defrost communication group are
working together and are coordinating their defrost processes in order to reach an optimum defrost
result. A defrosting controller is locking the remaining controllers of the group (Cooling request- and
defrost suppression). In this way the occurance of cost intensive load peaks, as well as influences
due to secondary air flows are avoided.The following processes are carried out, depending on the
selected defrosting method.
For electric defrosting, if the configuration "EL" is selected under "cD". If the controllers detect that
!
one controller of their defrost communication group has started a defrosting process, all the
remaining controllers are switched to standby. In the irregular case, the cancelling of the standby
state is done after the defrosting time exceeds 90 minutes.. After cancelling the signal, the next
defrosting process for thecontrollers that where switched to standby before is only allowed after one
hour or if the setpoint temperature was reached.
For hot gas defrosting in interconnected and individual refrigeration systems if the configuration
!
"HGE" or "HGS" is selected under "cd". Network defrost communication in combination with hot
gas defrosting is not implemented in this software version.
Recirculating air defrosting if the configuration "FAN" is selected under "cD". If the controllers of a
!
defrost communication group percieve that one controller of their group has started a defrosting
process, all the remaining controllers initiate a defrosting process for themselves. The cooling
process can only be initiated again after all controllers of the concerned defrosting group have
finished their defrosting process or if a safety time of 90 minutes is exceeded. After resuming the
cooling process the next defrosting can be initiated after a total of 2 hours cooling request (per
controller) at the earliest.
You can obtain more information on defrost communication with its various possible applications
directly from Cool Expert on request.
Defrost communication "Off" (OFF)
No network based defrost communication.
Note:
The defrost communication using the digital inputs is disabled when a defrost communication group
is set.
Support group
Parameter only valid in combination with "ndG", "1" or higher , hot gas defrost
"-2-", "cd", "HGE" or "HGS" and electrical defrost "-2-","cd", "EL"
nUG
W E
In preparation: this parameter has currently no function!
Operating level 2.1
(Internal heat control)
1
Heating control activated, value 1-15
OFF
No internal heat control
(Internal standby delay)
30
Value 1 - 900 seconds
Std
Standard
The first menu item after changing to the
cS
configuration level (operating level 2)
Operating level 2.2
The network level
(Network defrost group)
2
Adjustable value 1 - 8
OFF
Defrost Communication "Off"
(Network support group)
1
Adjustable value 1 – 8
OFF
No support group configured
8