Static UPS / Inverters are sophisticated devices and must be treated accordingly. Keep the Static
UPS in a non-condensing, well-ventilated environment, ensuring there is no ingress of moisture
or foreign material.
Location
Static UPS should be kept as close as possible to the battery in order to keep the battery cables
short. However do not locate the Static UPS in the same compartment as non-sealed batteries
since the gas from battery generator gases is very corrosive and can damage electronic
equipment and other items.
Important Precaution
The output side of the Static UPS AC wiring should never be connected to a generator or
incoming utility power. This condition is far worse than a short circuit. If the unit survives this
condition, it will shut down until correction is made.
An independent circuit breaker (MCB/MCCB) is suggested for INPUT & OUTPUT according to
the CEIL Static UPS capacity.
For Input, Output, battery wire thickness refers to table below.
UPS (KVA)
2.5 KVA-36/48 VOLT
3 KVA-36/48 VOLT
5 KVA-48/96/120/180 VOLT
7.5 KVA-120/180 VOLT
10 KVA-180/192 VOLT
12 KVA-192 VOLT

GETTING STARTED

I/P WIRE
THICKNESS
(sq. mm)
2.5
2.5
6
10
10
16
O/P WIRE
BATTERY
THICKNESS
THICKNESS
(sq. mm)
(sq. mm)
2.5
2.5
6
10
10
16
WIRE
10
16
10
16
10
16