Input Ohms
0
x 10
Ohms
474
x 10
Ohms
607
x 10
Ohms
910
x 10
Ohms
1210
x 10
Ohms
1540
x 10
Ohms
1860
x 10
Ohms
2150
x 10
Ohms
2360
x 10
Ohms
2400
x 10
Ohms
32767
x 10
Ohms
Figure 8: Example Custom Table
for a Sample Slidepot
(Tested Resistance Entered on the Left)

Digital Outputs

The G4106 provides four digital outputs which are wired
as shown as shown in Figures 5 and 6. These outputs are
described as follows: 24 VAC or VDC maximum, each
configurable as dry contact and as normally open or
normally closed.
Contact Rating: 3 Amp maximum

Procedure

1.
Turn the G4106's power switch OFF.
2.
Terminate the output wiring to the right termination
strip as shown in Figures 5 and 6.
NOTE: Pilot relays should NOT be powered from
the same transformer which powers the GX boards.
3.
Turn the G4106's power switch ON.

Manual Operation

By setting the HOA switches (see Figure 9), each digital
output can be placed in ON, OFF, or AUTO mode. The
position of the HOA switches may be monitored through
channels 81-88. Channel 81 corresponds to channel 11,
channel 82 corresponds to channel 12, etc. A status of
OFF on these channels indicates the switch is set to AUTO
mode. A status of ON indicates the switch is set to either
ON or OFF mode.
Rev (29-AUG-97) • Module Driver v4.7
Input Value
=
-1.00
=
-1.00
=
-0.75
=
-0.50
=
-0.25
=
0.00
=
0.25
=
0.50
=
0.75
=
1.00
=
1.00

Analog Outputs

The G4106 provides six analog outputs. These outputs
are described as follows.
Voltage Mode (0-10 VDC): 1k Ohm minimum load
impedance.
Current Mode (4-20 mA):
While the G4106's analog outputs are designed to output
voltage, it is possible to use these outputs to drive current
mode devices. To do this, wire a 1/2 Watt resistor in series
with the resistive load, as shown in Figures 5 and 6. The
value of the series resistor is determined as follows:
NOTE: If your load resistance is greater than 500 ohms,
your full scale output will be less than 20 mA.
Example: We want to drive a 100 Ohm resistive load
with a 0-20 mA signal. To find the value of the series
resistor, subtract the load resistance from 500 Ohms:
R
R
This example is shown in Figures 5 and 6.
Procedure
1.
2.
3.
8
Figure 9: G4106's HOA Switch
R
= 500 Ohms - R
SERIES
= 500 Ohms - R
SERIES
LOAD
= 500 Ohms - 100 Ohms = 400 Ohms
SERIES
Turn the G4106's power switch OFF.
Terminate the output wiring to the right termination
strip as shown in Figure 3.
Turn the G4106's power switch ON.
© 1995-97 Automated Logic Corporation
LOAD