LED 24 Output Power - indicates power is
being received from field termination board
from the external power supply for binary
outputs and isolated binary inputs.
Table 10. LED Signals
Run LED
Error LED
2 flashes
Off
per second
2 flashes
1 flash,
per second
then pause
2 flashes
2 flashes,
per second
alternating
with Run
LED
2 flashes
2 flashes,
per second
in sync
with Run
LED, then
pause
2 flashes
3 flashes,
per second
then off
2 flashes
4 flashes,
per second
then pause
2 flashes
On
per second
5 flashes
On
per second
5 flashes
Off
per second
7 flashes
7 flashes
per second
per second,
alternating
with Run
LED
14 flashes
14 flashes
per second
per second,
alternating
with Run
LED
Revised 7/10/01 • InterOP8500
Condition
Normal
Normal, but module is
alone on the CMnet
(this sequence doesn't
occur in WebCTRL)
Five minute auto-restart
delay after system error
Module is configured for a
different baud rate than the
rest of the network
segment
Module has just been
formatted
Two or more devices on
this network have the
same ARC156 network
address
Exec halted after frequent
system errors or GFBs
halted
Exec start-up aborted, Boot
is running
Firmware transfer in
progress, Boot is running
Ten second recovery
period after brownout
Brownout
Protection
The InterOP8500 module is protected by
internal solid state Polyswitches on the
incoming power and network connections.
These Polyswitches are not replaceable and
will reset themselves if the condition that
caused the fault returns to normal.
Production Date
To determine when a module was
manufactured, check the module status
report for the module in WebCTRL or
SuperVision. Refer to the appropriate user's
guide for more information about the module
status report.
A sticker on the back of the module also
shows the date the module was
manufactured. The first three characters on
the sticker indicate the type of module. The
next two characters show the year and month
of manufacture.
19