4. Use Figure 12 to wire a LogiStat, LogiStat
Plus, or LogiStat Pro to the S6104.
1
2 3 4
Gnd
Sw
Temp LS5v
1 2 3 4
Figure 12. LogiStat Wiring
Strip 1/4 inch of the ends of the wires (see
Figure 13).
1. Insert wire
into opening
Figure 13. Flip Lever Wiring
5. Turn the S6104's power switch on.
Digital Outputs
The S6104 has 6 digital outputs which can be
connected to a maximum of 24 Volts AC/DC
(see Figure 14). Each digital output is a dry
contact (rated at 3A maximum).
Be sure the S6104's power is off before wiring
any inputs or outputs. Connect the output
wiring to the screw terminals on the module.
Revised 7/30/02 • S6104
LogiStat Port
S6104
LogiStat
2. Press black
tab down to
connect wire
Power
Auto Off On
12
DO-6
11
10
DO-5
9
8
DO-4
7
6
DO-3
5
4
DO-2
3
2
DO-1
1
Figure 14. Digital Outputs
To verify each output's operation, lock the
output to a known condition using the
Function Block's Properties page in WebCTRL
or Parameter page in SuperVision. Be sure the
equipment operates as specified.
Each digital output can be placed in Manual
(on or off) or Auto mode by setting the HOA
switches (see Figure 1 on page 2 for the
switches' location). Table 5 on page 12 shows
the status of the digital output based on the
output's configuration and the HOA switch
position.
You can monitor the status of the HOA
switches through WebCTRL or SuperVision. In
WebCTRL, assign each switch a digital input
in the FB using the point number and the HOA
Status Feedback point type.
In SuperVision, assign each switch a digital
input in the FB using channel numbers 81
through 86. Channel 81 corresponds to HOA
switch number one, channel 82 corresponds
to HOA switch two, and so on.
An off status means the HOA switch is in Auto
mode. An on status means the HOA switch is
in Manual mode.
11