Automated Logic M4106nx Instrukcje techniczne - Strona 3

Przeglądaj online lub pobierz pdf Instrukcje techniczne dla Kontroler Automated Logic M4106nx. Automated Logic M4106nx 10 stron.

Specifications

Power 24VAC ± 10%, 50-60Hz (24VAC
±10%, 60Hz for UUKL Smoke Control
Systems), 20VA power consumption
single Class 2 source only, 100VA or less.
Inputs ten universal inputs, configurable
for 0-5VDC, 0-20mA, or thermistor.
Input Resolution 12 bit A/D.
Digital Outputs four digital outputs, relay
contacts rated at 3A resistive @ 24VAC.
Configurable as normally open or
normally closed.
Analog Outputs six analog outputs, 0-
10VDC.
Output Resolution 8 bit D/A.
Communication 156 kbps ARCNET, 9600
bps or 38.4 kbps CMnet.
Environmental Operating Range 0° to
130°F (-17.8° to 54.4°C); 10 to 90%
relative humidity, non-condensing. (For
UUKL Smoke Control Systems, 32 to
120.2 °F [0 to 49 °C]; 10 to 85% relative
humidity, non-condensing.)
Status Indication Visual (LED) status of
CMnet communication, running, errors,
and power.
Memory 1MB Flash memory and 1MB non-
volatile battery-backed RAM.
Protection Voltage, current, and ESD
protection on incoming power and
CMnet.
Battery Seven-year lithium BR2325 battery
provides a minimum of 10,000 hours of
data retention during power outages.
Listed by UL 916 (PAZX), cUL C22.2 No.
205-M1983 (PAZX7), FCC Part 15 -
Subpart B - Class A.

Mounting

Screw the M4106nx into an enclosed panel
using the mounting holes provided on the
cover plate. Be sure to leave about 2 inches (5
centimeters) on each side for wiring.
Revised 3/29/00 • M4106nx

Addressing

Before setting or changing the address, make
sure the M4106nx's power is off. The
M4106nx only reads the address when the
module is turned on. After changing the
address, you must transfer memory to the
module. Refer to "Transferring Memory" on
page 9.
The M4106nx has two rotary switches for
assigning the module's CMnet address. One
switch corresponds to the tens digit and the
other corresponds to the ones digit. For
example, if the module's address is three, set
the tens switch to zero and the ones switch to
three, as shown in Figure 2.
10 's
Figure 2. Setting the module's address

Power Wiring

Whenever possible, make sure the module's
power and communications connections are
working properly before connecting any input
or output points.
CAUTION The M4106nx module is a Class
2 device (less than 30VAC, 100VA maximum).
Take appropriate isolation measures when
mounting the M4106nx module in a control
panel where non-Class 2 devices (for
example, 120VAC) or wiring are present.
You can power several modules from the
same transformer if you maintain the same
polarity.
The M4106nx's operating range is 21.6VAC to
26.4VAC. If voltage measured at the module's
3
© 2000 Automated Logic Corporation
1's